Hardware Configuration

4.2 Device Configuration

The Device Configuration function allows you to set up the ISGS relay to match line frequency, phase sequence, and breaker connection settings of your system.

4.3 Setting Binary Input Voltages

Binary inputs are jumpered to correspond to the auxiliary supply voltage of the relay in which they are installed. The inputs will correctly respond to DC or AC depending on the jumpering. The jumpers can be placed to allow the inputs to work with any of the available voltages, independent of the auxiliary supply voltage. Refer to Figure 4.5 and Table 4.1.

4

125 VDC Bus

13

ISGS 21 Relay 22

12

BI 1

120VAC Aux Relay

120 VAC Source to be Monitored

1000

Device Configuration

 

Address

Parameter

Options

1002

Frequency

50Hz or 60Hz

1003

Phase Sequence

123 (ABC) or 132 (ACB)

1004

Breaker

Trip 1, Trip 2, Trip 3, Trip 1 & 2,

 

Connection

Trip 1

& 3, Trip 2 & 3, or

 

 

Trip 1

& 2 & 3

1005

Trip Time

0.01-32.00 s (0.01 s steps)

 

 

 

 

The frequency parameter (1002) must be set to the nominal frequency of your system. Phase sequence (1003) selects the phase sequence of your system as it enters the ISGS relay. The breaker connection parameter (1004) selects the trip contact that your breaker is connected to. Many func- tions use this parameter to determine if the device is attempting to open the breaker. Breaker failure can be initi- ated by either one of the three trips (if the Breaker Failure function is enabled). The default is set to Trip 1.

Figure 4.4 Binary Inputs Independent of Supply Voltage

Table 4.1 lists the possible jumper positions for setting binary input voltages. The numbers in this table each refer to a pin from and to which a jumper can be moved.

Table 4.1 Jumper Positions

Voltage

BI 1

BI 2

BI 3

BI 4

Supply

Terminals

Terminals

Terminals

Terminals

 

21/22

23/22

25/26

27/28

 

 

 

 

 

48 V

X111-X112

X23-X22

X34-X35

X46-X47

 

 

 

 

 

 

X13-X14

X25-X26

X37-X38

X49-X50

 

 

 

 

 

 

X16-X17

X28-X29

X40-X41

X52-X53

 

 

 

 

 

 

X19-X20

X31-X32

X43-X44

X55-X56

 

 

 

 

 

125 V

X111-X112

X23-X22

X34-X35

X46-X47

(Default)

 

 

 

 

X13-X14

X25-X26

X37-X38

X49-X50

 

 

 

 

 

 

 

X17-X18

X29-X30

X41-X42

X53-X54

 

 

 

 

 

 

X19-X20

X31-X32

X43-X44

X55-X56

 

 

 

 

 

120 VAC

X110-X111

X24-X23

X35-X36

X47-X48

 

 

 

 

 

 

X14-X15

X26-X27

X38-X39

X50-X51

 

 

 

 

 

 

X17-X18

X29-X30

X41-X42

X53-X54

 

 

 

 

 

 

X20-X21

X32-X33

X44-X45

X56-X57

 

 

 

 

 

250 VDC

X111-X112

X23-X22

X34-X35

X46-X47

 

 

 

 

 

h

X14-X15

X26-X27

X38-X39

X50-X51

 

 

 

 

X17-X18

X29-X30

X41-X42

X53-X54

 

 

 

 

X19-X20

X31-X32

X43-X44

X55-X56

16

Siemens Energy & Automation, Inc.

Page 22
Image 22
Siemens SG8158-00 manual Device Configuration, Setting Binary Input Voltages