ISGS Settings Worksheet for

Date:

Set A

 

 

 

S

3000

Alarm Setpoints

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3100

Demand Setpoints

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3101

Demand Interval

15

 

30

 

60

minutes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3102

Sync time

0

 

15

 

30

45

minutes after hour

 

 

 

 

 

 

 

 

 

 

 

 

 

3103

Subperiods 60

1

 

2

 

3

 

4

6

12

 

 

 

 

 

 

 

 

 

 

 

 

 

3104

Subperiods 30

1

 

2

 

3

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3105

Subperiods 15

1

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3106

Current Average Demand

Enabled

 

 

 

 

Disabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3107

Current Average Demand Pickup

3000 A

 

Range: 0-9999 A (1 A steps)

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

3108

KW Demand

Enabled

 

 

 

 

Disabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3109

KW Demand Pickup

100000 kW

 

Range: 0-999,999 kW

 

kW

 

 

(1 kW steps)

 

 

 

 

 

 

 

 

 

 

 

 

3200

Power Setpoints

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3201

KVAR Function

Enabled

 

 

 

 

Disabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3202

KVAR Pickup

100000 kVAR

Range: 0-999,999 kVAR

 

kVAR

 

(1 kVAR steps)

 

 

 

 

 

 

 

 

 

 

 

 

3203

KVAR Time Delay

1800 s

 

Range: 0-3600 s

(1 s steps)

 

s

 

 

 

 

 

 

 

 

 

 

 

 

 

3204

KVA Function

Enabled

 

 

 

 

Disabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3205

KVA Pickup

100000 kVA

 

Range: 0-999,999 kVA

 

kVA

 

 

(1 kVA steps)

 

 

 

 

 

 

 

 

 

 

 

 

3206

KVA Time Delay

1800 s

 

Range:

0-3600 s

(1 s steps)

 

s

 

 

 

 

 

 

 

 

 

 

 

 

 

3207

PF Lead Function

Enabled

 

 

 

 

Disabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3208

PF Lead Pickup

0.8

 

 

Range:

0.2-1.0 (0.1 steps)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3209

PF Lead Sign

Lag

 

 

 

 

Lead

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3210

PF Lead Delay

1800 s

 

Range:

0-3600 s

(1 s steps)

 

s

 

 

 

 

 

 

 

 

 

 

 

 

 

3211

PF Lag Function

Enabled

 

 

 

 

Disabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3212

PF Lag Pickup

0.8

 

 

Range:

0.2-1.0 (0.1 steps)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3213

PF Lag Sign

Lag

 

 

 

 

Lead

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3214

PF Lag Delay

1800 s

 

Range:

0-3600 s

(1 s steps)

 

s

 

 

 

 

 

 

 

 

 

 

 

 

 

S-8

 

 

 

 

 

 

 