User Interface

3.4 Menu

The ISGS relay menu (or memory map) is organized in a hier- archical structure that is made up of address blocks and addresses. The first level consists of address blocks. Each address block represents one complete function or two related functions and is identified by a unique four-digit num- ber ending in two zeros (for example, 1500). Refer to Figure 3.1.

The second level consists of individual addresses confined to an address block. Each address represents a part of a func- tion—the changeable parameter—or the measured value of a displayed parameter. The parameter is identified by a unique four-digit number that consists of the first two digits of the address block and two digits indicating the parame- ter’s number within the address block (for example, 1502). Refer to Figure 3.1.

Block

Function

Address

Parameter

 

 

 

 

A1500

Instantaneous

1501

Function 50

 

Phase Overcurrent

1502

Pickup 50

 

(50)

1504

Delay 50

 

 

1510

Freeze Wfm 1 50

 

 

1511

Freeze Wfm 2 50

 

 

1512

Block 50

 

High-Set Instanta-

1551

Function 50HS

 

neous Phase Over-

1552

Pickup 50HS

 

current (50HS)

1560

Freeze Wfm 1 HS

 

 

1561

Freeze Wfm 2 HS

 

 

 

 

A1900

Directional Phase

1901

Function

 

Time Overcurrent

1902

Curve

 

(67)

1903

Pickup

 

 

1905

Time Dial

 

 

1906

Filter

 

 

1907

Impedance

 

 

1908

Direction

 

 

1910

Freeze Wfm 1

 

 

1911

Freeze Wfm 2

 

 

 

 

A2200

Overvoltage (59)

---

---

 

 

 

 

Figure 3.1 Example of Menu Structure Displaying Address Blocks with Two Related Functions, an Individual Function, and an Unavailable Function.

A complete ISGS relay menu with parameter listing is pro- vided in Appendix C. The various parameter settings are shown in the respective section describing the complete function.

Only certain protective function parameters have two set- tings. All A settings are grouped under parameter set A, and all B settings are grouped under parameter set B. Each parameter set automatically includes all the regular parame- ters that can be programmed to only one setting at a time and, therefore, apply to both sets. Examples are protective function enable settings and matrixed output contacts such as waveform buffers and blocking. For more information on parameter sets, refer to Section 6.11.

The LCD identifies functions that include parameters config- urable for A and B settings by preceding the function’s address block number with the letter A or the letter B, depending on which parameter set is currently displayed. Refer to Figure 3.2.

A1500 Instantaneous

Phase Overcurrent 50

Figure 3.2 LCD Display of a Function that Includes Parameters Configurable for A and B Settings.

In addition, when scrolling through the individual parameters of an ISGS relay, the LCD identifies each parameter that is configurable for A and B settings by preceding the parame- ter’s address number with the letter A or the letter B, depending on which parameter set is currently displayed. Refer to Figure 3.3

A1502 Pickup 50

110A

Figure 3.3 LCD Display of a Parameter that is Configurable for A and B Settings

When accessing the ISGS relay menu through the keypad, the Arrow keys allow scrolling through all available functions and parameters. If an option is not installed, the LCD only displays the address block that is reserved for this option. In this case, second level addresses are not available.

3.5 Standard Operating Procedures

Before attempting to display or configure any of the relay data, ensure that the relay has control power which is indi- cated by the system LED (green) being lit.

The steps for displaying data, configuring parameters, saving data, and switching to the alternate parameter set for either display or configuration are described in detail in Table 3.1, Standard Operating Procedures.

3

Siemens Energy & Automation, Inc.

11

Page 17
Image 17
Siemens SG8158-00 manual Menu, Standard Operating Procedures, A1500 Instantaneous Phase Overcurrent, A1502 Pickup 110A