ISGS Settings Worksheet for

Date:

Set B

 

 

 

B1500

Instantaneous Phase Overcurrent (50)

 

 

 

 

 

 

High-Set Instantaneous Phase Overcurrent (50HS)

 

 

 

 

 

 

 

 

 

 

 

 

 

B1501

Function 50

 

Enabled

 

 

Disabled

 

 

 

 

 

 

 

 

 

 

B1502

Pickup 50

5 A CT

1.0 A

Range: 1-120 A (0.1 A steps)

 

A

 

 

 

 

 

 

 

 

 

 

1 A CT

0.2 A

Range: 0.2-24 A (0.1 A steps)

 

A

 

 

 

 

 

 

 

 

 

B1504

Time Delay 50

 

0.00 s

Range: 0-60 s

(0.01 s steps)

 

s

 

 

 

 

 

 

 

 

1510

Freeze Waveform 1 50

 

Settings displayed or changed here apply to both parameter sets

 

 

 

 

 

 

 

 

1511

Freeze Waveform 2 50

 

Settings displayed or changed here apply to both parameter sets

 

 

 

 

 

 

 

 

 

B1512

Block 50 by

 

None

50HS & 50HSN

 

50HS

 

50HSN

 

 

 

 

 

 

 

 

 

B1551

Function 50HS

 

Enabled

 

 

Disabled

 

 

 

 

 

 

 

 

 

 

B1552

Pickup 50HS

5 A CT

5.0 A

Range: 5-120 A (0.1 A steps)

 

A

 

 

 

 

 

 

 

 

 

 

1 A CT

0.2 A

Range: 0.2-24 A (0.1 A steps)

 

A

 

 

 

 

 

 

 

1560

Freeze Waveform 1 50HS

Settings displayed or changed here apply to both parameter sets

 

 

 

 

 

 

 

1561

Freeze Waveform 2 50HS

Settings displayed or changed here apply to both parameter sets

 

 

 

 

 

 

 

 

B1600

Instantaneous Neutral or Ground Overcurrent (50N)

 

 

 

 

 

High-Set Instantaneous Neutral or Ground Overcurrent (50HSN)

 

 

 

 

B1601

Function 50N

 

Enabled

 

 

Disabled

 

 

 

 

 

 

 

 

 

 

B1602

Pickup 50N

5 A CT

1.0 A

Range: 1-120 A (0.1 A steps)

 

A

 

 

 

 

 

 

 

 

 

 

1 A CT

0.2 A

Range: 0.2-24 A (0.1 A steps)

 

A

 

 

 

 

 

 

 

 

 

B1604

Time Delay 50N

 

0.00 s

Range: 0-60 s

(0.01 s steps)

 

s

 

 

 

 

 

 

 

1610

Freeze Waveform 1 50N

Settings displayed or changed here apply to both parameter sets

 

 

 

 

 

 

 

1611

Freeze Waveform 2 50N

Settings displayed or changed here apply to both parameter sets

 

 

 

 

 

 

 

 

 

B1612

Block 50N by

 

None

50HS & 50HSN

 

50HS

 

50HSN

 

 

 

 

 

 

 

 

 

B1651

Function 50HSN

 

Enabled

 

 

Disabled

 

 

 

 

 

 

 

 

 

 

B1652

Pickup 50HSN

5 A CT

5.0 A

Range: 5-120 A (0.1 A steps)

 

A

 

 

 

 

 

 

 

 

 

 

1 A CT

0.2 A

Range: 0.2-24 A (0.1 A steps)

 

A

 

 

 

 

 

 

 

1660

Freeze Waveform 1 50HSN

Settings displayed or changed here apply to both parameter sets

 

 

 

 

 

 

 

1661

Freeze Waveform 2 50HSN

Settings displayed or changed here apply to both parameter sets

 

 

 

 

 

 

 

 

 

S-18

Siemens Energy & Automation, Inc.

Page 104
Image 104