Appendix A: Trip Curves & Equations

100

 

 

 

10

 

TimeDial

(Seconds)

 

 

 

 

9.9

 

 

7.0

toTrip

1

 

5.0

 

 

 

 

3.0

Time

 

 

1.5

 

 

 

 

 

 

0.5

0.1

 

 

 

 

 

0.1

0.01

 

 

 

1

10

50

Multiples of Pickup

 

1000

 

 

 

100

 

 

toTrip(Seconds)

10

 

TimeDial

 

 

Time

 

 

9.9

1

 

7.0

 

 

 

 

 

 

5.0

 

 

 

3.0

 

 

 

1.5

 

0.1

 

0.5

 

 

 

 

 

 

0.1

 

0.01

 

 

 

1

10

50

Multiples of Pickup

Figure A.9 Definite Inverse Curve (SEA8)

Figure A.10 I-Squared-T Curve

A

A.4 I-Squared-T Curve

The ISGS provides an I-Squared-T characteristic in addition to the standard inverse curves.

 

 

Trip Characteristic

 

 

 

 

 

 

50.7D + 10.14

 

 

 

 

 

T = -------------------------------------

 

 

 

 

 

 

i

2

 

 

 

 

 

 

---

 

 

 

 

 

 

 

i

p

 

 

 

 

 

 

 

 

Reset Characteristic

 

 

 

 

 

i

 

 

 

 

 

trD

 

 

 

 

 

 

 

 

 

 

 

For ----< 1:

 

T =

 

 

 

 

 

 

----------------------

 

 

 

ip

 

 

 

i

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

---

1

 

T = time to trip, in seconds

 

 

 

 

ip

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

--i--

⎟ = multiple of pickup setting

 

 

 

 

i

p

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D = time dial setting, 0.1 to 9.9 in steps of 0.1 tr = reset constant = 7.4

Equation A.4 I-Squared-T Equation

A.5 Custom Protective Curve

The custom curve consists of up to 60 current-time pairs corresponding to points on the time-current characteristic curve. Current refers to multiple-of-pickup value (I/Ip) on the horizontal axis, and time refers to time-to-trip values on the vertical axis. Each point consists of two values (I/Ip and t), loaded in order from lowest to highest value of I/Ip via the SEAbus or local ports. Siemens Wisdom software is required in order to load a custom curve. Time-to-trip has a range of

0.00to 655.35 seconds in steps of 0.01 seconds. I/Ip has a range of 1.1 to 20.00 in steps of 0.01. The first point in the data set must be I/Ip=1.1, the last point must be I/Ip=20.

Points in between these two limits can be for any values of I/ Ip and t as long as the slope (Δt/(ΔI/Ip)) of the curve described by the points is between 0 (horizontal) and -∞ (ver- tical). For input current in excess of 20 x Ip, the relay will enter a definite time mode and the curve will be considered to be flat (constant time) at the time value associated with I/ Ip=20. Once loaded, a custom curve is not adjustable, that is there is no time dial adjustment.

A.6 Over/Undervoltage Curves

The ISGS provides a moderately inverse overvoltage and a moderately inverse undervoltage protection defined by the equation in Equation A.5 and Equation A.6. Their charac- teristics are provided in Figure A.11 and Figure A.12.