User Interface
Table 3.1 | Standard Operating Procedures | ||
|
|
| |
Step |
| Task | Description |
|
|
|
|
|
|
| Display Data |
|
|
|
|
1 |
| Display data at | Use Double Arrow keys to scroll forward or backward between address blocks. |
|
| Address Block | OR |
|
| (xx00) | |
|
| Press Direct Addr key; enter address of desired address block using the numeric keypad; press Enter key. | |
|
|
| |
|
|
| To view passwords, carry out step 4 before continuing with the next step. |
|
|
|
|
2 |
| Display data at | Use Single Arrow keys to scroll forward or backward between parameter addresses. |
|
| Address | Skip step 3 if function has no subaddresses. |
|
| (xxxx) | |
|
|
| |
|
|
| OR |
|
|
| Press Direct Addr key; enter address of desired parameter using the numeric keypad; press Enter key. |
|
|
| Skip step 3 if function has no subaddresses. |
|
|
|
|
3 |
| Display data at | Press F key once to enter subaddress level; use Single Arrow keys to scroll forward or backward between |
|
| Subaddress | subaddresses. |
|
| (0xx) | Press F key again to return to address level. |
|
|
| |
|
|
|
|
|
|
| Configure Parameters |
|
|
|
|
4 |
| Enter Password | Press Password key; enter the password; press Enter key twice to return to screen displayed last before |
|
|
| password entry. |
|
|
| Leaving an address block, leaving a function within an address block, or before scrolling to the waveform |
|
|
| parameters within a function prompts for renewed password entry. |
|
|
| For password levels, proper password entry, and display messages, refer to Section 3.3. |
|
|
|
|
5 |
| Configure at | Display cursor is blinking (otherwise repeat step 4). |
|
| Address | Change displayed value by entering a new value using the keypad. Press Enter key. |
|
| (xxxx) | |
|
| Change displayed selection by pressing the No key to scroll forward through options until desired option | |
|
|
| |
|
|
| appears. Press Enter key. |
|
|
| Skip step 6 if function has no subaddresses. |
|
|
|
|
6 |
| Configure at | Press F key once to enter subaddress level; use Single Arrow keys to scroll forward or backward between |
|
| Subaddress | subaddresses. |
|
| (0xx) | Change displayed selection by pressing No key to scroll forward through options until desired option appears. |
|
|
| |
|
|
| Press Enter key. |
|
|
| Press F key again to return to address level. |
|
|
|
|
|
|
| Save Changes |
|
|
|
|
7 |
| Enter Save | Press F key. At the blinking cursor position, the letter F is displayed. Press Enter key. Message “SAVE NEW |
|
| Procedure | SETTINGS?” appears. |
|
|
|
|
|
| Undo Changes | To abort any changes made, press No key. After message “SAVING PROCEDURE ABORTED” appears, |
|
|
| press Enter key to return to screen displayed last before aborting settings. |
|
|
| Settings can be undone any time while still in the same function by simply returning to the parameter and |
|
|
| assigning a new value. |
|
|
|
|
|
| Save Changes | To save settings and reset relay to new parameters, press Yes key followed by Enter key. After message |
|
|
| “NEW SETTINGS SAVED” appears, press Enter key to return to screen displayed last before saving settings. |
|
|
| Leaving an address block, leaving a function within an address block, or before scrolling to the waveform |
|
|
| parameters within a function prompts for the saving of the function settings. |
|
|
|
|
|
|
| Switch Parameter Set |
|
|
|
|
8 |
| Switch | Press F key followed by either “1” (for normal settings) or “2” (for alternate settings) on the numeric keypad. |
|
| Parameter Set | The message “PARAMETER SET COPIED TO EDIT” appears. Press Enter key. |
9Display/Config- Display shows address block (“xx00”) with either “A” or “B” prefix in address (“Axx00” or “Bxx00”).
ure Alternate | “A” indicates parameter set 1; “B” indicates parameter set 2. |
Parameter Set | Repeat steps 1 to 3 or steps 1 to 7 to display or configure the alternate parameter set. |
|
3
Siemens Energy & Automation, Inc. | 13 |