ISGS Settings Worksheet for

Date:

Set A

 

 

 

3400

Value Supervision

 

 

 

 

 

 

 

 

 

 

 

 

Disabled

3401

Voltage Balance Function

Enabled

 

 

 

 

 

 

100 V

 

 

 

3402

Voltage Balance Pickup

 

Range:

40-120 V (0.1 V steps)

 

 

 

0.80

Range:

0.58-0.95

 

3404

Voltage Balance Factor

 

 

 

(0.01 teps)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Disabled

3411

Current Sum Function

 

Enabled

 

 

 

 

 

 

0.5 A

 

 

 

 

3412

Current Sum Pickup

5 A CT

Range:

0.5-5 A

(0.1 A steps)

 

 

1 A CT

0.1 A

Range:

0.1-1 A

(0.1 A steps)

 

 

 

 

 

0.10

Range:

0.10-0.95

 

3414

Current Sum Factor

 

 

 

(0.01 steps)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Disabled

3411

Current Balance Function

Enabled

 

 

 

 

 

 

2.5 A

 

 

 

 

3412

Current Balance Pickup

5 A CT

Range:

0.5-5 A

(0.1 A steps)

 

 

1 A CT

0.1 A

Range:

0.1-1 A

(0.1 A steps)

 

 

 

 

 

0.80

Range:

0.10-0.95

 

3414

Current Balance Factor

 

 

 

(0.01 steps)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3500

Breaker Operation

 

 

 

 

 

 

 

 

 

 

 

 

Disabled

3501

Interrupted Current Function

Enabled

 

 

 

 

 

 

 

 

 

3502

Interrupted Current Pickup

1000.00 kA

Range: 0-9999.9 kA

(1 kA steps)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Disabled

3503

Breaker Operations Functions

Enabled

 

 

 

 

 

100

 

 

 

 

3504

Breaker Operations Counter

Range:

0-65535

 

 

 

 

 

 

 

 

 

 

V

A

A

A

A

kA

S