Siemens SG8158-00 manual Figure A.11 Moderately Inverse Overvoltage Curve

Models: SG8158-00

1 121
Download 121 pages 35.55 Kb
Page 63
Image 63

Appendix A: Trip Curves & Equations

 

 

 

 

 

 

Over/Undervoltage Coefficients

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Curve Type

 

Des.

 

A1

 

B1

 

 

 

N1

tr

 

Inverse

 

 

 

 

 

 

0.51

 

-1.75

 

 

0.50

---

 

 

 

 

 

 

 

 

 

 

 

 

Mod. Inverse

 

 

0.51

 

-0.45

 

 

0.50

---

 

 

 

 

 

 

 

 

 

 

 

 

 

￿￿Very Inverse

 

 

 

0.51

 

1.75

 

 

0.50

---

 

 

 

 

 

 

 

 

The A, B, and N coefficients are for the standard relay formula

 

 

 

 

 

 

 

 

 

Table A.2 Under/Overvoltage Coefficients

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

v

1.5:

 

 

 

AD

 

 

For1.01 ≤ -----

 

T = ------------------------ + BD

 

 

 

 

 

 

vp

 

 

 

v

 

N

 

 

 

 

 

 

 

 

 

 

 

-----

1

 

 

 

 

 

 

 

 

 

 

 

 

vp

 

 

 

 

 

 

v

:

 

 

AD

 

 

 

For⎜

----- > 1.5

 

T = ------------------------- + BD⎟

 

 

 

vp

 

 

( 1.5 )

N

1

 

 

 

 

 

 

 

 

 

 

 

 

T = time to trip, in seconds

 

 

 

 

 

 

v = measured input voltage

 

 

 

 

 

 

vF= pickup value (tap setting)

 

 

 

 

 

 

v

 

 

 

 

 

 

 

 

 

 

 

 

------

⎟ = multiple of pickup setting

 

 

 

 

 

 

v

p

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D = time dial setting, 0.1 to 9.9 in steps of 0.1

 

 

A, B, N = constants for inverse curves

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Equation A.5 Overvoltage Equation

1000

(Seconds)

100

 

 

 

 

 

 

 

TimeDial

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.0

 

 

 

 

 

 

 

 

9.9

toTrip

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Time

 

 

 

 

 

 

 

2.0

1

 

 

 

 

 

 

 

1.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.1

 

0.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

1.1

1.2

1.3

1.4

1.5

1.6

Multiples of Pickup

Figure A.11 Moderately Inverse Overvoltage Curve

1000

A

For 0.5 -----v≤ 1.5:

T =

------------------------

AD

+ BD

 

 

vp

 

⎛ v

 

N

 

 

 

 

 

v----p-

1

 

 

 

 

 

 

 

For⎜ -----v0.5:

T = -------------------------

AD

 

 

+ BD⎟

 

vp

( 1.5 )

N

1

 

 

 

 

 

 

T = time to trip, in seconds

 

 

 

 

 

 

v = measured input voltage

 

 

 

 

 

 

vF= pickup value (tap setting)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

--v----

⎟ = multiple of pickup setting

 

 

 

 

 

v

p

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D = time dial setting, 0.1 to 9.9 in steps of 0.1 A, B, N = constants for inverse curves

Time Dial

9.9

5.0

2.0

1.0

0.5

0.2

0.1

100

(Seconds)

10 Tripto

Time

1

0.1

0.4

0.5

0.6

0.7

0.8

0.9

1.0

Multiples of Pickup

Equation A.6 Undervoltage Equation

Figure A.12 Moderately Inverse Undervoltage Curve

 

Siemens Energy & Automation, Inc.

57

Page 63
Image 63
Siemens SG8158-00 manual Figure A.11 Moderately Inverse Overvoltage Curve