Data Acquisition

7.3.2Voltage Minimum/Maximum Log

The Voltage Minimum/Maximum Log function allows the dis- play of minimum and maximum values measured by the relay. The collected information is compared against previ- ously stored values and the log is updated. All logged values are time stamped and resetting the log (see Section 6.7) will reset all log values. No voltages are metered unless the VT option is installed.

4700

Voltage Minimum/Maximum Log

Address

Data

Description

4701

V12 min

Minimum phase voltage

 

 

between phases A and B

4702

V12 max

Maximum phase voltage

 

 

between phases A and B

4703

V23 min

Minimum phase voltage

 

 

between phases B and C

4704

V23 max

Maximum phase voltage

 

 

between phases B and C

4705

V31 min

Minimum phase voltage

 

 

between phases C and A

4706

V31 max

Maximum phase voltage

 

 

between phases C and A

4713

VAv min

Minimum average voltage

4714

VAv max

Maximum average voltage

4717

MinTHD

Minimum value of estimated

 

 

total harmonic distortion

4718

MaxTHD

Maximum value of estimated

 

 

total harmonic distortion

 

 

 

The MinTHD and MaxTHD parameters (4717 and 4718) dis- play the minimum or maximum total harmonic distortion cal- culation for the average current. The calculation is an estimate of the harmonics on the system rather than an exact measurement.

4800

Power Minimum/Maximum Log

Address

Data

Description

4801

kW min

Minimum power value

4802

kW max

Maximum power value

4803

kW dem min

Minimum active power demand

 

 

value

4804

kW dem max

Maximum active power demand

 

 

value

4805

kVA min

Minimum kilovolt-ampere value

4806

kVA max

Maximum kilovolt-ampere value

4807

kVAR min

Minimum kilovolt-ampere

 

 

reactive value

4808

kVAR max

Maximum kilovolt-ampere

 

 

reactive value

4809

PF max

Maximum power factor value

4810

PF min

Minimum power factor value

 

 

 

7.3.4Frequency Minimum/Maximum Log

The Frequency Minimum/Maximum Log function allows the display of minimum and maximum values measured by the relay. The collected information is compared against previ- ously stored values and the log is updated. All logged values are time stamped, and resetting the log (see Section 6.7) will reset all log values.

4900

Frequency Metering

Address

Data

Description

4901

Fmin

Minimum frequency value

4902

Fmax

Maximum frequency value

 

 

 

7

7.3.3Power Minimum/Maximum Log

The Power Minimum/Maximum Log function allows the dis- play of minimum and maximum values measured by the relay. The collected information is compared against previ- ously stored values and the log is updated. All logged values are time stamped, and resetting the log (see Section 6.6) will reset all log values. No voltages are metered unless the VT option is installed.