Data Acquisition

7

7.4 Metered Data

Metered data is stored by the ISGS relay and can be dis- played by accessing address blocks 4100 to 4900. The dis- play of this data does not require a password. You can display the same data more conveniently by using Wisdom software described in Chapter 8.

7.4.1Current Values

The Current Metering function stores the metered current and current demand values for the ISGS relay. The relay will measure and display the rms values of the current for the three phases and ground or neutral. The ISGS relay also shows total harmonic distortion as a percentage of the fun- damental for the three phase current inputs. This function displays undefined when the measured components are below the total harmonic distortion threshold.

4100

Current Metering

 

Address

Data

Range￿

4101

I Phase A

0-250% ICT

4102

I Phase B

0-250% ICT

4103

I Phase C

0-250% ICT

4104

I Neutral

0-250% ICT

4105

I Average

0-250% ICT

4106

I Demand Phase A

0-250% ICT

4107

I Demand Phase B

0-250% ICT

4108

I Demand Phase C

0-250% ICT

4109

I Demand Average

0-250% ICT

￿ 4110

THD Current

0-250% ICT

 

 

 

ICT = primary CT rating

7.4.2Voltage Values

The Voltage Metering function allows the display of metered voltage data for the ISGS relay. The rms voltage measure- ments for this function depend on the selected VT connec- tion method, either line-to-ground or line-to-line. The relay also shows total harmonic distortion as a percentage of the fundamental for the three phase voltage inputs. It displays undefined when the measured components are below the total harmonic distortion threshold. This function is only avail- able if the voltage input option is installed.

4200

Voltage Metering

 

Address

Data

Range￿

4201

V Phases A-B

10-125% Vn

4202

V Phases B-C

10-125% Vn

4203

V Phases C-A

10-125% Vn

4204

V L-L Average

10-125% Vn

￿ 4209

THD Volts

10-125% Vn

IVT = primary VT rating

7.4.3Power Values

The Power Metering function stores the metered voltage data for the ISGS relay. This function is only available if the voltage input option is installed.

4300

Power Metering

 

Address

Data

Range

4301

kW 3-Phase

0-999,999.99 kW

4302

kW Hours

0-999,999.99 kWHR

4303

kW Demand

0-999,999.99 kWD

4304

kVA 3-Phase

0-999,999.99 kVA

4305

kVAR 3-Phase

0-999,999.99 kVAR

4306

kVAR Hours

0-999,999.99 kVARH

 

 

 

4307

PF

-1 — 0 — +1

 

 

 

7.4.4Frequency Values

The Frequency Metering function allows the display of the system frequency. This function is only available if the voltage input option is installed.

4400

Frequency Metering

Address

Data

Range

4401

Frequency

45-65 Hz

 

 

 

46

Siemens Energy & Automation, Inc.

Page 52