Hardware Configuration

4.4 CT Configuration

The CT Configuration function allows you to set up the ISGS relay to match the phase CT primary rating, the neutral or ground CT primary rating, and the CT input’s normal power flow setting of your system. For CT connections refer to Figure 4.8.

4

Main Bus

ISGS

 

 

ISGS

Power

Power

Normal Power Flow

Reverse Power Flow

(Into CT Polarity Mark)

(Out of CT Polarity Mark)

Figure 4.6 Normal/Reverse Power Flow

4.5 VT Configuration

Use this address block to configure the ISGS relay to match the VT primary rating and the VT connection setting for your system. These settings are available only if the voltage input option is installed on the relay.

1100

CT Configuration

 

Address

Parameter

Options

1101

Phase CT Primary

5-8000 A (1 A steps)

 

Rating

 

1102

Neutral or Ground

5-8000 A (1 A steps)

 

CT Primary Rating

 

1104

Power Flow

Normal or Reverse

 

 

 

The phase (1101) and neutral/ground (1102) CT primary rat- ings are independently configurable. However, when a resid- ual sensing method is used for ground fault protection, the primary current ratings for the neutral CT and the phase CT must be equal. The CT secondary ratings (1A or 5A) are set at the factory and are not changeable from the front panel.

Power flow is also referred to as top feed or bottom feed. If the power enters the polarity mark on the CTs, set the Power Flow parameter (1104) to Normal. If power leaves the polarity mark, enter Reverse. Figure 4.6 illustrates examples of nor- mal and reverse power flow.

18

Siemens Energy & Automation, Inc.

Page 24
Image 24
Siemens SG8158-00 manual CT Configuration, VT Configuration