Glossary
address Unique
address block Unique
average line voltage Arithmetic average of AB, BC, CA
average phase current Arithmetic average of phase A, B, and C currents. (IA+IB+IC)/3 = IAVG.
average phase voltage Arithmetic average of A, B, and C phase voltages
binary input Optically isolated voltage level sensor with a fixed threshold. The input is considered activated if voltage above the threshold is applied and
binary output ANSI rated dry output contact that can be matrixed to a binary input of a protective function for closing.
Breaker Failure (50BF) Relay function that responds to a fault condition where any phase current being measured by a CT does not drop below a programmed level. Whenever another protective function activates the contact identified by the breaker parameter, this function will wait until the set amount of time has expired. Then it checks the phase cur- rents. If they are not equal to or less than the set pickup value, the function executes its defined actions.
Breaker Mechanism Relay function that can be enabled to sense a breaker mechanism error and cause an action to be taken and an event being logged if the a- and
Caution Indicates a potentially hazardous situation which, if not avoided, could result in moderate or minor injury.
Comm Event Relay function that can be set to allow the remote activation of the breaker and binary outputs.
CT Configuration A function to set up the ISGS relay to match phase CT primary rating, neutral or ground CT primary rating, and the CT input's normal power flow settings of an electrical distribution system.
Current Balance Relay function that protects against an unbalance in the phase currents. The function monitors the phase currents for approximate balance (of equal magni- tude). Balance is defined as the ratio of minimum to maxi- mum current, where the maximum current is the largest and the minimum current the smallest of the three phase cur- rents. The current is considered balanced and will not cause
an alarm. The function monitors for balance when the maxi- mum current is larger than the current balance pickup value. An alarm occurs when the min/max ratio is smaller than the current balance factor.
current sensor Toroidal current transformer providing cur- rent level data and operating power for fault protection and metering. Its rated primary current establishes the maximum continuous current rating of the circuit breaker. Its rated sec- ondary current is 0.5 A at rated primary current. Sensors used in Static Trip III trip units are encapsulated in polymeric material to protect the windings and prevent motion during short circuit fault conditions.
Curve Parameter of several ISGS protective functions that allows the selection of a definite time delay or a characteristic curve.
custom curve A |
|
|
|
| |
Danger Indicates an imminently hazardous situation which, |
| ||||
if not avoided, will result in death or serious injury. |
|
|
|
| |
Device Configuration A function to set up the ISGS relay |
| ||||
to match line frequency, phase sequence, and breaker con- |
| ||||
nection settings of an electrical distribution system. |
|
|
|
| |
Directional Neutral or Ground Time Overcurrent (67N) |
| ||||
Relay function that protects against neutral or ground time |
| ||||
overcurrent condition. This function uses a selected time |
| ||||
overcurrent characteristic curve to determine the trip time, |
| ||||
and the voltages present on the VTs to determine the current |
| ||||
direction. Tripping occurs when the neutral or ground current |
| ||||
exceeds the programmed pickup at 100% or drops below |
| ||||
the pickup at 95% for a period of time equal to the delay time |
| ||||
setting. The pickup must remain active for the entire delay |
| ||||
time for a trip to occur. If the overcurrent condition subsides |
| ||||
in less time than the delay time, the pickup will go inactive |
| ||||
and the directional neutral or ground overcurrent function will |
| ||||
reset. When tripping occurs, the actual condition that caused |
| ||||
the trip is recorded in the device's nonvolatile trip log. |
|
|
|
| |
Directional Phase Time Overcurrent (67) | Relay func- |
| |||
tion that protects against a phase overcurrent condition. This |
| ||||
function uses a selected time overcurrent characteristic |
| ||||
curve to determine the trip time, and the voltages present on |
| ||||
the VTs to determine the current direction. Tripping occurs |
| ||||
when any one phase current exceeds the programmed |
| ||||
pickup at 100% or drops below the pickup at 95% for a |
| ||||
period of time equal to the delay time setting. The pickup |
| ||||
must remain active for the entire delay time for a trip to occur. |
| ||||
If the overcurrent condition subsides in less time than the |
| ||||
delay time, the pickup will go inactive and the directional |
| ||||
phase overcurrent function will reset. When tripping occurs, |
| ||||
the actual condition that caused the trip is recorded in the |
| ||||
device's nonvolatile trip log. |
|
|
|
|
|
event log Chronological record of significant | events | that |
|
| |
|
| ||||
occur during relay operation. Includes operation and | fault | G | |||
events. |
|
|
|
| |
|
|
|
|
| |
|
|
|
|
|
|
Filter Parameter of several ISGS protective functions that sets the sensing
Siemens Energy & Automation, Inc. |