Siemens SG8158-00 manual Isgs Settings Worksheet for Date

Models: SG8158-00

1 121
Download 121 pages 35.55 Kb
Page 92
Image 92

ISGS Settings Worksheet for

Date:

Set A

 

 

 

A2400

Phase Sequence Voltage (47)

 

 

 

 

 

 

 

 

Negative Sequence Voltage (47N)

 

 

 

 

 

 

A2401

Function 47

Enabled

 

 

 

 

Disabled

 

 

 

 

 

 

 

 

 

2410

Freeze Waveform 1 47

---

 

on Trip

 

 

None

 

 

 

 

 

 

 

 

2411

Freeze Waveform 2 47

---

 

on Trip

 

 

None

 

 

 

 

 

 

 

 

 

A2451

Function 47N

Enabled

 

 

 

 

Disabled

 

 

 

 

 

 

 

 

 

 

A2452

Curve 47N

Inverse

 

 

 

 

Definite Inverse

 

 

 

 

 

 

 

A2453

Pickup 47N

10%

Range: 4-40% (1% steps)

%

 

 

 

 

 

 

 

A2454

Time Delay 47N(Defin.)

0.00 s

Range: 0-100 s (0.01 s steps),

s

or ∞

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A2455

Time Dial 47N (Inverse)

0.10

Range:

0.1-9.9

(0.1 steps)

 

 

 

 

 

 

 

 

 

 

A2456

Maximum Time (Inverse)

120 s

Range:

1-250 s

(1 s steps)

s

 

 

 

 

 

 

 

A2457

Block 47N by

40 V

Range: 40-120 V (1 V steps)

V

 

 

 

 

 

 

 

 

2460

Freeze Waveform 1 47N

on pickup

 

on Trip

 

 

None

 

 

 

 

 

 

 

 

2461

Freeze Waveform 2 47N

on pickup

 

on Trip

 

 

None

 

 

 

 

 

 

 

 

 