Siemens SG8158-00 manual Isgs Settings Worksheet for Date Set B

Models: SG8158-00

1 121
Download 121 pages 35.55 Kb
Page 107
Image 107

ISGS Settings Worksheet for

Date:

Set B

 

 

 

B2200

Overvoltage (59)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B2201

Function 59

Enabled

 

 

 

Disabled

 

 

 

 

 

 

 

 

 

B2202

Curve 59

Inverse

Moderately

 

Very Inverse

Definite Inverse

Inverse

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B2203

Pickup Source Voltage 59

Line-to-Line

 

 

 

Line-to-Neutral

 

(if VT mode is (L-N)

 

 

 

 

 

 

 

 

 

 

 

 

B2204

Pickup 59

130 V

Range:

60-250 V (0.1 V steps)

 

V

 

 

 

 

 

 

 

 

 

B2205

Time Delay 59 (Definite)

0.10 s

Range:

0-60 s

(0.01 s steps),

 

s

or ∞

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B2206

Time Dial 59 (Inverse)

0.1

Range:

0.1-9.9

(0.1steps)

 

 

 

 

 

 

 

 

 

2210

Freeze Waveform 1 59

Settings displayed or changed here apply to both parameter sets

 

 

 

 

 

 

 

2211

Freeze Waveform 2 59

Settings displayed or changed here apply to both parameter sets

 

 

 

 

 

 

 

 

 

B2300

Undervoltage (27)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B2301

Function 27

Enabled

 

 

 

Disabled

 

 

 

 

 

 

 

 

 

B2302

Curve 27

Inverse

Moderately

 

Very Inverse

Definite Inverse

Inverse

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B2303

PU Source V 27

Line-to-Line

 

 

 

Line-to-Neutral

 

(if VT mode is (L-N)

 

 

 

 

 

 

 

 

 

 

 

 

B2304

Pickup 27

50.0 V

Range:

40-230 V (0.1 V steps)

 

V

 

 

 

 

 

 

 

 

B2305

Time Delay 27 (Definite)

0.10 s

Range:

0-60 s (0.01 s steps),

 

s

or ∞

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B2306

Time Dial 27 (Inverse)

0.1

Range:

0.1-9.9

(0.1 steps)

 

 

 

 

 

 

 

 

 

2310

Freeze Waveform 1 27

Settings displayed or changed here apply to both parameter sets

 

 

 

 

 

 

 

2311

Freeze Waveform 2 27

Settings displayed or changed here apply to both parameter sets

 

 

 

 

 

 

 

 

 

S

Siemens Energy & Automation, Inc.

S-21

Page 107
Image 107
Siemens SG8158-00 manual Isgs Settings Worksheet for Date Set B