Protective Function Configuration

The Directional Phase Time Overcurrent function can be enabled or disabled (1901).

The Curve parameter (1902) allows the selection of the pre- programmed characteristic curve used by this function. The ISGS relay comes with nine standard overcurrent character- istic curves that can be adjusted with the Time Dial parame- ter. The custom curve is a user-definable protective curve that integrates with instantaneous reset. The lower limit of the custom curve is 1.10. The maximum time to trip is the time at 1.10.

The range of the pickup value (1903) depends on the sec- ondary phase CT rating (1 A or 5 A) and the value is in sec- ondary amperes. The function begins timing when any individual phase current exceeds the pickup current setting.

The Time Dial parameter (1905) used for the selected curve allows the time-to-trip of the curve to be raised or lowered The dial can be adjusted from 0.1 to 9.9 in steps of 0.1.

The Filter parameter (1906) sets the sensing method used by the function in its pickup calculations. The rms filter uses fun- damental current plus harmonics, while the fundamental filter ignores harmonics.

Impedance (1907) sets the angle used by this function. Impedance determines the direction of current flow being measured and can be set from 0 to 90 degrees. The direc- tional characteristic (line) in the complex impedance plane is shown in Figure 5.2. The directional characteristic is always perpendicular to the line impedance vector.

The sensing direction (1908) can be set to forward or reverse. The forward setting allows the directional protection element to pickup on fault current only in the direction oppo- site to normal power flow.

Each of the two waveform capture buffers (1910 and 1911) can be independently programmed to freeze snapshots on pickup or trip.

The function is able to actuate any binary output contact on pickup, and any trip or binary output contact on trip.

5.10Directional Neutral or Ground Time Overcurrent (67N)

The Directional Neutral or Ground Time Overcurrent function uses a selected time overcurrent characteristic curve to determine the trip time for the applied current at the fourth current input, utilizing the voltages present on the VTs to determine current direction. The defined characteristic curves are valid over a range of multiple of pickup values. The function also includes a customer defined curve. Refer to Appendix A for detailed trip curve information. This func- tion is only available if the voltage input option is installed.

A2000

Directional Neutral or Ground Time Overcurrent

 

(67N)

 

Address

Parameter

Option

2001

Function

Enabled or Disabled

2002

Curve

Inverse

 

 

Short Inverse

 

 

Long Inverse

 

 

Moderately Inverse

 

 

Custom

 

 

Very Inverse

 

 

Extremely Inverse

 

 

Definite Inverse

 

 

Slightly Inverse

 

 

I2T Without Limit

2003

Pickup

5 A CTs: 0.5-20 A or

 

 

1 A CTs: 0.1-4 A

 

 

(0.1 A steps)

2005

Time Dial

0.1-9.9 (0.1 steps)

2006

Filter

rms or fundamental

2007

Impedance

0-90°

2008

Direction

Forward or Reverse

2010

Freeze Wfm1

on Pickup, on Trip, or None

2011

Freeze Wfm2

on Pickup, on Trip, or None

 

 

 

The Directional Neutral or Ground Time Overcurrent function can be enabled or disabled (2001).

The Curve parameter (2002) allows the selection of the pre- programmed characteristic curve used by this function. The ISGS relay comes with nine standard overcurrent character- istic curves that can be adjusted with the time dial parameter (see below). The custom curve is a user-definable protective curve that integrates with instantaneous reset. The lower limit of the custom curve is 1.10. The maximum time to trip is the time at 1.10.

5

Figure 5.2 Directional Characteristic

Siemens Energy & Automation, Inc.

25

Page 31
Image 31
Siemens SG8158-00 manual Directional Neutral or Ground Time Overcurrent 67N