Protective Function Configuration
5
protective curve that integrates with instantaneous reset. The lower limit of the custom curve is 1.10. The maximum time to trip is the time at 1.10.
The range of the pickup value (1803) depends on the sec- ondary phase CT rating (1 A or 5 A) and the value is in sec- ondary amperes.
The Time Dial parameter (1805) used for the selected curve allows the
The Filter parameter (1806) sets the sensing method used by the function in its pickup calculations. The rms filter uses fun- damental current plus harmonics, while the fundamental filter ignores harmonics.
The Reset parameter (1709) offers instantaneous or disk emulation settings. Selecting Instantaneous causes the relay to clear the timer when the current drops below the pickup threshold. Selecting Disk Emulation causes the relay to simu- late the integrating disk characteristics of electromechanical relays, where the delay time decays over time. With disk emulation, a relay that continuously picks up and drops out will eventually trip. Set this parameter to Instantaneous when using a custom curve.
Each of the two waveform capture buffers (1810 and 1811) can be independently programmed to freeze snapshots on pickup or trip.
The function is able to actuate any binary output contact on pickup, and any trip or binary output contact on trip.
5.8Blocking Capability for Breaker or Interrupter Saving
This function is used to keep an
50HS/N can also be matrixed to an output contact to block differential tripping of a transformer differential relay when a fault is between the interrupter and the high side (bushings) of the transformer.
Figure 5.1 Blocking Capability Diagram
5.9 Directional Phase Time Overcurrent (67)
The Directional Phase Time Overcurrent function uses a selected time overcurrent characteristic curve to determine the trip time for the applied phase currents, utilizing the volt- ages present on the VTs to determine current direction. The defined characteristic curves are valid over a range of multi- ple of pickup values. The function also includes a customer defined curve. Refer to Appendix A for detailed trip curve information. This function is only available if the voltage input option is installed.
A1900 | Directional Phase Time Overcurrent (67) | |
Address | Parameter | Option |
1901 | Function | Enabled or Disabled |
1902 | Curve | Inverse |
|
| Short Inverse |
|
| Long Inverse |
|
| Moderately Inverse |
|
| Custom |
|
| Very Inverse |
|
| Extremely Inverse |
|
| Slightly Inverse |
|
| Definite Inverse |
|
| I2T Without Limit |
1903 | Pickup | 5 A CTs: |
|
| 1 A CTs: |
|
| (0.1 A steps) |
1905 | Time Dial | |
1906 | Filter | rms or fundamental |
1907 | Impedance | |
1908 | Direction | Forward or Reverse |
1910 | Freeze Wfm 1 | on Pickup, on Trip, or None |
1911 | Freeze Wfm 2 | on Pickup, on Trip, or None |
|
|
|
24 | Siemens Energy & Automation, Inc. |