ISGS Settings Worksheet for

Date:

Set B

 

 

 

S

B2400

Phase Sequence Voltage (47)

 

 

 

 

 

 

 

 

 

Negative Sequence Voltage (47N)

 

 

 

 

 

 

 

B2401

Function 47

Enabled

 

 

 

Disabled

 

 

 

 

 

 

 

 

 

 

2410

Freeze Waveform 1 47

Settings displayed or changed here apply to both parameter sets

 

 

 

 

 

 

 

 

 

 

2411

Freeze Waveform 2 47

Settings displayed or changed here apply to both parameter sets

 

 

 

 

 

 

 

 

 

 

 

 

B2451

Function 47N

Enabled

 

 

 

Disabled

 

 

 

 

 

 

 

 

 

 

 

 

B2452

Curve 47N

Inverse

 

 

 

Definite Inverse

 

 

 

 

 

 

 

 

 

 

B2453

Pickup 47N

10%

Range: 4-40% (1% steps)

 

%

 

 

 

 

 

 

 

 

 

B2454

Time Delay 47N(Defin.)

0.00 s

Range: 0-100 s (0.01 s steps),

 

s

 

or ∞

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B2455

Time Dial 47N (Inverse)

0.1

Range:

0.1-9.9

(0.1 steps)

 

 

 

 

 

 

 

 

 

 

 

 

 

B2456

Maximum Time (Inverse)

120 s

Range:

1-250 s

(1 s steps)

 

s

 

 

 

 

 

 

 

 

 

B2457

Block 47N by

40 V

Range: 40-120 V (1 V steps)

 

V

 

 

 

 

 

 

 

 

 

2460

Freeze Waveform 1 47N

Settings displayed or changed here apply to both parameter sets

 

 

 

 

 

 

 

 

 

 

2461

Freeze Waveform 2 47N

Settings displayed or changed here apply to both parameter sets

 

 

 

 

 

 

 

 

 

 

 

 

B2500

Overfrequency (81O)

 

 

 

 

 

 

 

 

Underfrequency (81U)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B2501

Function 81O

Enabled

 

 

 

Disabled

 

 

 

 

 

 

 

 

 

 

 

B2502

Pickup 81O

62.0 Hz

Range:

60.1-65.0 Hz

Hz

 

(0.1 Hz steps)

 

 

 

 

 

 

 

 

 

 

 

 

B2504

Time Delay 81O

0.10 s

Range: 0-100 s (0.01 s steps),

s

 

or ∞

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2506

Block 81O

40 V

Range: 40-120 V (1 V steps)

V

 

 

 

 

 

 

 

 

 

2510

Frz. Wfm1 81O

Settings displayed or changed here apply to both parameter sets

 

 

 

 

 

 

 

 

 

 

2511

Frz. Wfm2 81O

Settings displayed or changed here apply to both parameter sets

 

 

 

 

 

 

 

 

 

 

 

 

B2551

Function 81U

Enabled

 

 

 

Disabled

 

 

 

 

 

 

 

 

 

 

 

B2553

Pickup 81U

58.0 Hz

Range:

55.0-59.9 Hz

 

Hz

 

(0.1 Hz steps)

 

 

 

 

 

 

 

 

 

 

 

 

B2554

Delay 81U

0.10 s

Range: 0-100 s (0.01 s steps),

 

s

 

or ∞

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B2556

Block 81U

40 V

Range:

40-120 V (1 V steps)

 

V

 

 

 

 

 

 

 

 

 

2560

Freeze Waveform 1 81U

Settings displayed or changed here apply to both parameter sets

 

 

 

 

 

 

 

 

 

 

2561

Freeze Waveform 2 81U

Settings displayed or changed here apply to both parameter sets

 

 

 

 

 

 

 

 

 

 

 