Control & Communications

6

6.4 Trip Contacts

The ISGS relay offers up to three trip contacts which are monitored by the microprocessor. Trip contacts may be con- figured by the user to trip the relay based on any of a number of functions. Trip contact reaction time is about 4.5 ms.

The relay displays the options at each matrix position in the sequence listed in the table below.

6400

Trip Contacts

 

 

Address

Para-

Matrix

Option

Option (cont.)

meter

Position

6401

Contact 1

001

not matrixed

59 Trip

 

 

to

BI1

47 Trip

 

 

020

BI2

OvrBrOps PU

 

 

 

BI3

OBrAmps PU

 

 

 

BI4

OvrAmps-

 

 

(Options

OC Trip

Dmd PU

 

 

apply to

NonOC Trip

OkWDmd PU

 

 

each

Relay Tripped

OvrkVAR PU

 

 

matrix

50HS Trip

OvrkVA PU

 

 

position)

50HSN Trip

PFLag PU

 

 

 

81O Trip

PFLead PU

 

 

 

81U Trip

50BF Trip

 

 

 

47N Trip

TrScMon PU

 

 

 

50 Trip

TrCoilCont PU

 

 

 

50N Trip

BrMech PU

 

 

 

51 Trip

CommEvent 1

 

 

 

51N Trip

CommEvent 2

 

 

 

67 Trip

CommEvent 3

 

 

 

67N Trip

CommEvent 4

 

 

 

27 Trip

CommEvent 5

6402

Contact 2

001-020

(same as Contact 1 above)

6403

Contact 3

001-020

(same as Contact 1 above)

 

 

 

 

 

6.5 Comm Events

Protective functions are internally generated events that can trip a relay. For the protection to function properly, the pro- cessor interprets these events (inputs) and makes a decision. Communication (Comm) events are externally generated messages that can trip a relay without any interpretation. This remote communication allows Comm events to control outputs (contacts), such as opening a breaker; or switch parameter sets if matrixed to a binary input. Comm events are sent from a PC or other devices on the RS-232 or RS-485 networks.

Comm events can be blocked (disabled) with binary inputs to prevent remote parameterization during service periods or as a general safety measure. Refer to the list of binary inputs in Section 6.2.

6.6 Breaker Monitoring

To increase the security of the protective system, it is helpful to monitor several parameters directly from the switchgear. The ISGS relay can monitor the components such as the 52a and the 52b switches, the traditional circuit breaker position lamps, and the tripping voltage supply.

The 52a and 52b switches have a total of four possible posi- tion combinations which can be decoded as illustrated in Table 6.1. The 52a and 52b switches referred to are those which traditionally provide indication of circuit breaker posi- tion (52b) and trip coil continuity (52a). All error reporting can be enabled and disabled, and the actions to be taken are configurable.

Table 6.1 52a and 52b Switches Decoding

52a Switch

52b Switch

Condition Registered

Position

Position

 

 

 

 

Open

Open

Trip Coil Continuity Error, or

 

 

Breaker Withdrawn

 

 

 

Open

Closed

Circuit Breaker Open

 

 

 

Closed

Open

Breaker Closed

 

 

 

Closed

Closed

Circuit Breaker Mechanism Error

 

 

 

The ISGS relay monitors:

breaker position

trip coil continuity

trip source impedance.

Breaker position is sensed through dedicated binary inputs that monitor the 52a and 52b switches on the breaker mech- anism (breaker mounted). Trip coil continuity is monitored by continually sensing a current that flows through the trip coil. Trip source impedance is checked using a switchable elec- tronic load across the trip voltage supply.

8300

Breaker Monitoring

Address

Function/

Options

 

Parameter

 

8301

TripSrcImp

Enabled or Disabled

8302

TripSrcFail

Yes or No

8303

TrpCoil Cont

Enabled or Disabled

8304

TrpCoilFail

Yes or No

8305

BrkrMech

Enabled or Disabled

 

 

 

Exceptions to the normal operating conditions include the presence of push-to-test switches across either the a-switch, b-switch, or both. A push-to-test switch across the b-switch will produce a false indication of a breaker mecha- nism error when the breaker is actually closed. A push-to test switch across the a-switch (and hence across the trip solenoid) will produce a false indication of a breaker mecha- nism error when the breaker is actually closed.

34

Siemens Energy & Automation, Inc.

Page 40
Image 40
Siemens SG8158-00 manual Trip Contacts, Comm Events, Breaker Monitoring