ISGS Settings Worksheet for

Date:

Set A

 

 

 

This ISGS settings worksheet allows easy recording of the desired ISGS parameter settings when configuring the device manually with the keypad controls.

Functions and parameters are listed in numerical sequence of their address blocks and addresses just as they appear on the LCD. Where applicable, value ranges and resolution are provided for easy reference. Only configurable functions and parameters are listed. For a complete list refer to the ISGS relay menu in Appendix C.

Before configuring the device, copy this form and enter the desired configuration data. Include the device identification number (device version number and its catalog number on front panel label; or line 1 and line 2 of Power On display) and the date of configuration. Then simply circle the desired set-

tings and enter numerical values in the blank spaces pro- vided. Boldfaced settings indicate factory defaults. For indicating matrix settings, draw a line from the matrix position number to the desired setting and circle the setting.

Take special care in copying lines 1 and 2 of the relay’s Power On display (refer to Section 4.1). The information dis- played in these two lines provides Siemens with detailed information about the device in the event you encounter a problem and have to contact Siemens customer service.

After entering all data on this configuration form, take it to the device and enter the information into the relay. This form allows for the recording of both parameter sets. After com- pleting this form, file it for future reference.

0000

Power On Display (enter display)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

----

Line 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

----

Line 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1000

Device Configuration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1002

Frequency

60 Hz

 

 

 

 

50 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1003

Phase Sequence

123 (ABC)

 

 

 

 

132 (ACB)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1004

Breaker Connection

Trip1

Trip2

 

Trip3

 

Trips 1&2

Trips1&3

Trips 123

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1005

Trip Time

0.1 s

 

Range: 0.01-32 s

 

 

s

 

 

 

(0.01 s steps)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1100

Current Transformer Configuration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1101

Phase CT Primary Rating

1200 A

 

 

Range: 5-8000 A

 

A

 

 

 

 

(1 A steps)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1102

Neutral CT Primary Rating

1200 A

 

 

Range: 5-8000 A

 

A

 

 

 

 

(1 A steps)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1104

Power Flow

Normal

 

 

 

 

Reverse

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1200

Voltage Transformer Configuration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S

 

 

 

 

 

 

 

 

 

 

 

1201

Primary Rating

12000 V

 

Range: 120-138000 V

 

V

 

 

(1 V steps)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1202

VT Mode

Line-to-Line

 

 

 

Line-to-Neutral

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1203

Secondary VT Rating

120 V

 

Range: 100-120 V

(1 V steps)

 

V

 

 

 

 

 

 

 

 

 

 

 

 

 

 