Communication

Industrial Ethernet

Industrial Wireless LAN (IWLAN)

Overview

OS clients

PCS 7

Web server

Design

SCALANCE W746-1PRO Ethernet client module

SCALANCE

X414-3

Engineering station

OS-LAN

(terminal bus)

SCALANCE

X204-2/X208

Redundant

OS server

Access point

SCALANCE W788-1PRO

 

Ethernet

 

 

Client module

 

Mobile remote client

SCALANCE

Stationary

with WLAN interface

W746-1PRO

remote client

The SCALANCE W746-1PRO Ethernet client module is highly suitable for integrating devices with an Industrial Ethernet con- nection into Industrial Wireless LAN (IWLAN) radio networks with reliable communication. The SCALANCE W746-1PRO Ethernet client module handles the radio connection for a maximum of eight connected devices with Ethernet interface. If one of the connected devices is exchanged, the Ethernet client module recognizes this immediately and administers the new address.

 

SIMATIC PCS 7 allows you to integrate mobile or stationary

 

 

remote clients into the OS-LAN (terminal bus) via a SCALANCE

9

W788-1PRO access point.

The following applications can be implemented in this manner:

 

 

• Use of additional remote OS clients (1 or 2 on IWLAN)

 

• Linking of Web clients to a SIMATIC PCS 7 Web server (1 or

 

2 on IWLAN)

 

• Remote access to an engineering station with application of

 

Remote Desktop (Windows XP or Server 2003 operating sys-

 

tem) or PC Anywhere, e.g. during commissioning

 

Mobile remote clients (e.g. notebooks) possessing a WLAN in-

 

terface can communicate with the access point via it. Stationary

 

remote clients in a desktop/tower housing (SIMATIC PCS 7 In-

 

dustrial Workstations) require a SCALANCE W746-1PRO Ether-

 

net client module for the IWLAN communication with the access

 

point.

 

SCALANCE W746-1PRO Ethernet client module and

 

SCALANCE W788-1PRO access point are both very rugged,

 

use state-of-the-art authentication and encryption procedures,

 

and guarantee high reliability of the radio channel.

 

Note:

 

Please note that Industrial Wireless LAN is not approved of as a terminal

 

bus (OS-LAN) or plant bus of SIMATIC PCS 7.

Special features of the SCALANCE W746-1PRO Ethernet client module

Versatile power supply facilities (operation on 100 V to 240 V AC network with PS791-1PRO power supply)

Antenna diversity for reliable reception in complex radio envi- ronments with two ANT795-4MR omnidirectional antennas screwed onto the housing, can be replaced by other types from the SCALANCE W700 range

Transmission rate up to 54 Mbit/s at 2.4 GHz and 5 GHz with radio approval in more than 30 countries

Conforms to the IEEE 802.11b/g and IEEE 802.11a standards

High reliability through reservation of data transfer rate with IWLAN communication with SCALANCE W788-1PRO access point

WPA and 128-bit encryption (AES) for high security against il- legal access

Rugged metal enclosure resistant to shock and vibration, and with IP65 dust protection

Suitable for ambient temperatures from -20 to +60°C (resistant to condensation)

For further information and detailed technical specifications, re- fer to Catalog IK PI, the A&D Mall or Catalog CA 01 under "Com- munication/networks, SIMATIC NET communication systems, In- dustrial mobile communication".