© Siemens AG 2007

Process I/O

ET 200S distributed I/O

Introduction

 

 

 

Overview

Design

The ET 200S is a bit-modular distributed I/O system in IP 20 de- gree of protection and is approved for operation in Ex zone 2 or 22 (except for operation with motor starters). It is designed with independent wiring that supports the hot swapping of I/O modules (with fire certificate).

The range of I/Os that can be used with SIMATIC PCS 7 includes power modules for electronics modules and motor starters, ana- log and digital signal modules, and motor starters up to 7.5 kW.

The implementation of safety engineering applications is sup- ported by:

Safety-related F-components which are integrated in the SI- MATIC Safety Integrated System, e.g. terminal, power and electronics modules as well as motor starters

SIGUARD safety engineering for motor starter applications with conventional safety logic in plants of safety categories 2 to 4 (EN 954-1)

Note:

In addition to the selected modules, all other current ET 200S electronics modules can be used, but with limited functionality. Use of components from the SIPLUS extreme range in extended temperature ranges and under medial loading on request.

Main components of the ET 200S distributed I/O system:

 

Terminal modules enable the electrical and mechanical con-

 

nection of the I/O modules and carry the terminals for the pro-

 

cess wiring:

 

- TM-P terminal modules for power modules

 

- TM-E terminal modules for electronics modules

 

- TM-DS/TM-RS terminal modules for motor starters and

 

TM-xB expansion modules

 

IM 151 interface module for connecting the PROFIBUS DP to

 

the ET 200S station. The terminal module is included in the

 

scope of delivery.

 

Power modules for PM-E electronics modules and PM-D mo-

 

tor starters

 

- Individual grouping of load and sensor supply voltages and

11

their monitoring, as well as

for the safe shutting down of digital output modules

 

-Supplying and monitoring the auxiliary voltages for motor starters, as well as for the shutting down of a complete group of motor starters

Electronics modules for process data exchange

-Digital electronics modules for connecting digital sensors and actuators

-Analog electronics modules for connecting analog sensors and actuators

Motor starter modules for switching and protecting any three-phase loads

Accessories

-Reserve module for reserving a slot for any electronics mod- ule

-Label sheets for printing ID labels on a laser printer

-Shield connection: shield connecting element, shield termi- nal, ground terminal, copper voltage bus 3 x 10 mm; components for the low-impedance connection of cable shielding at low cost of installation

Siemens ST PCS 7 · November 2007

11/39

Page 253
Image 253
Siemens ST PCS 7 manual ET 200S distributed I/O, 11/39