Siemens ST PCS 7 manual Connection to plant bus, Connection to terminal bus OS-LAN

Models: ST PCS 7

1 344
Download 344 pages 20.13 Kb
Page 89
Image 89

© Siemens AG 2007

Operator system

Redundant operator systems

OS redundancy

Redundant OS single stations / OS servers with BCE communication

Redundant OS single stations / OS servers with CP 1613 communication

FastEthernet card

PCS 7 single station

redundancy or

PCS 7 server

redundancy

CP 1613

S7-1613 software

PCS 7 single station

redundancy or

PCS 7 server

redundancy

CP 1613

S7-1613 software

+ Upgrade

S7-REDCONNECT

PCS 7 single station

redundancy or

PCS 7 server redundancy

Plant bus

Plant bus

Plant bus

5

 

Max. 8 automation systems

Max. 64 automation systems

Fault-tolerant systems

per single station/pair of servers

per single station/pair of servers

AS 414H, AS 417H

Connection of redundant OS single stations / OS servers on the plant bus

Connection to plant bus

 

 

 

Selection and Ordering Data

Order No.

The operator systems (single stations or servers) communicate

 

 

 

Design of redundant OS single stations

with the automation systems via the Industrial Ethernet plant bus.

 

 

 

The following special points must be observed for redundant

SIMATIC PCS 7 Single Station

 

configurations:

Redundancy V7.0

 

• BCE communication via Ethernet network card

6 languages (German, English,

 

French, Italian, Spanish,

 

10/100/1000 Mbit/s is generally also sufficient for redundant

Chinese), executes with Windows

 

operator stations. Up to 8 automation systems can be con-

XP Professional, single license for

 

nected per pair of servers in this manner.

2 installations

 

• Communication using CP 1613 is only required in the follow-

with OS Software Single Station

 

and WinCC/Redundancy as well

 

ing cases:

 

as RS 232 connecting cable,

 

- Connection of a subordinate fault-tolerant automation sys-

10 m

 

tem

Type of delivery:

 

- More than 8 stations are required per OS.

2 license key disks, 2 emergency

 

• An operator station with CP 1613 is delivered with the S7-1613

key disks, certificate of license,

 

terms and conditions; PCS 7 V7.0

 

software. If a subordinate fault-tolerant automation system is

 

toolset DVDs, Microsoft

 

to be connected, the S7-REDCONNECT software is required.

SQL Server 2005 including EULA,

 

In this case, the S7-REDCONNECT upgrade must be ordered.

supplementary CDs/DVDs (e.g.

 

• If an operator station with BCE communication is to be up-

Microsoft ServicePacks and tools)

 

as well as RS 232 connecting

 

graded for operation with a subordinate fault-tolerant automa-

 

cable, 10 m

 

tion system, the S7-REDCONNECT software is required in ad-

 

 

• 250 POs

6ES7 652-3AA07-2YA0

dition to the CP 1613 communications processor.

 

• If the plant bus is to be designed as a redundant dual ring, you

 

• 1000 POs

6ES7 652-3AB07-2YA0

require two interface modules (2 x Ethernet network cards

 

• 2000 POs

6ES7 652-3AC07-2YA0

10/100/1000 Mbit/s or 2 x CP 1613) per OS single station /

 

• 3000 POs

6ES7 652-3AD07-2YA0

OS server.

 

 

 

 

Connection to terminal bus (OS-LAN)

You can connect clients and servers to a non-redundant terminal bus (OS-LAN) using the onboard Ethernet interface or a desktop adapter network card. With a redundant terminal bus where two rings are connected together via two pairs of switches, each sta- tion must be connected to both rings using a SIMATIC PCS 7 redundant terminal bus adapter package. The SIMATIC PCS 7 redundant terminal bus adapter package consists of server and desktop adapter network cards (for details on the configuration, refer to the Manual "SIMATIC PCS 7 V7.0 fault-tolerant process control systems").

• 5000 POs

6ES7 652-3AE07-2YA0

 

 

PowerPacks for PO expansion

 

See under OS Software Single

 

Station PowerPack V7.0

 

(2 PowerPacks each required)

 

 

 

Siemens ST PCS 7 · November 2007

5/17

Page 89
Image 89
Siemens ST PCS 7 manual Connection to plant bus, Connection to terminal bus OS-LAN, Design of redundant OS single stations