Siemens ST PCS 7 manual 10/28, AS 417F Single Station 6ES7 AS 412FH Redundant Station

Models: ST PCS 7

1 344
Download 344 pages 20.13 Kb
Page 208
Image 208

© Siemens AG 2008

Automation systems

Safety-related automation systems

Selection and ordering data

Order No.

Selection and ordering data

Order No.

 

AS 417F (Single Station)

6ES7 654-

AS 412FH (Redundant Station)

6ES7 656-

 

with SIMATIC PCS 7 AS Runtime license for

7 7 7 7 7 - 7 7 B 7

with SIMATIC PCS 7 AS Runtime license for

7 7 7 7 7 - 7 7 B 7

 

100 POs

100 POs

 

 

 

 

CPU with 2 interfaces (MPI/DP master and DP

 

2 x CPU with 1 interface each (MPI/DP master)

 

 

master)

 

2 x 768 KB RAM (512 KB each for program

 

 

 

 

 

 

30 MB RAM (15 MB each for program and

 

and 256 KB each for data)

 

 

data)

 

 

 

 

Type of delivery

 

Type of delivery

 

 

• Preassembled and tested

8

• Preassembled and tested

8

 

Memory card

 

Memory card

 

 

• Memory card 4 MB RAM (up to approx.

C

• 2 x memory card 1 MB RAM (up to approx.

A

 

300 POs)

 

50 POs)

 

 

• Memory card 8 MB RAM (up to approx.

D

• 2 x memory card 2 MB RAM (up to approx.

B

 

800 POs)

 

180 POs)

 

 

• Memory card 16 MB RAM (up to approx.

E

 

 

 

3,000 POs)

 

 

 

 

CPU type

 

CPU type

 

 

• CPU 417-4H with S7 F Systems RT license

N

• 2 x CPU 412-3H with S7 F Systems RT license

B

 

(up to approx. 2,500 POs)

 

(up to approx. 50 POs)

 

 

Additive interface modules

 

Sync modules and cables

 

 

• Without additive interface module

0

• 2 x 2 sync modules for distances up to 10 m

3

 

• 1 x IF 964-DP

1

and 2 x FO sync cable, 1 m

 

 

 

 

 

Interface module to

 

Interface module to

 

 

Industrial Ethernet plant bus1)

 

Industrial Ethernet plant bus1)

 

 

• 1 x CP 443-11)

1

• 2 x CP 443-1 for redundant interface module1)

1

 

• 2 x CP 443-1 for redundant interface module1)

2

• 2 x 2 CP 443-1 for 4-way connection1)

2

 

Rack

 

Rack

 

 

• UR2 (9 slots), aluminum

3

• 1 x UR2-H (2 x 9 slots), aluminum

1

 

• UR2 (9 slots), steel

4

• 1 x UR2-H (2 x 9 slots), steel

2

10

• UR1 (18 slots), aluminum

5

• 2 x UR2 (9 slots), aluminum

3

• UR1 (18 slots), steel

6

• 2 x UR2 (9 slots), steel

4

 

Power supply (without backup batteries)

 

Power supply (without backup batteries)

 

 

• 1 x PS 407, 10 A for 120/230 V AC/DC

B

• 2 x PS 407, 10 A for 120/230 V AC/DC

B

 

• 1 x PS 407, 10 A for 120/230 V AC/DC, redun-

C

• 2 x PS 407, 10 A for 120/230 V AC/DC, redun-

C

 

dancy possible

 

dancy possible

 

 

• 1 x PS 407, 20 A for 120/230 V AC/DC

D

• 2 x PS 407, 20 A for 120/230 V AC/DC

D

 

• 2 x PS 407, 10 A for 120/230 V AC/DC,

E

• 2 x 2 PS 407, 10 A for 120/230 V AC/DC,

E

 

redundancy possible

 

edundancy possible

 

 

• 1 x PS 405, 10 A for 24 V DC

G

• 2 x PS 405, 10 A for 24 V DC

G

 

• 1 x PS 405, 10 A for 24 V DC, redundancy

H

• 2 x PS 405, 10 A for 24 V DC, redundancy

H

 

possible

 

possible,

 

 

• 1 x PS 405, 20 A for 24 V DC

J

• 2 x PS 405, 20 A for 24 V DC

J

 

• 2 x PS 405, 10 A for 24 V DC, redundancy

K

• 2 x PS 405, 10 A for 24 V DC, redundancy

K

 

possible

 

possible

 

 

Additive PROFIBUS DP interface modules1)

 

Additive PROFIBUS DP interface modules1)

 

 

• Without CP 443-5 Extended

0

• Without CP 443-5 Extended

0

 

• 1 x CP 443-5 Extended

1

• 2 x CP 443-5 Extended

1

 

• 2 x CP 443-5 Extended1)

2

• 2 x 2 CP 443-5 Extended1)

2

 

• 3 x CP 443-5 Extended1)

3

• 2 x 3 CP 443-5 Extended1)

3

 

• 4 x CP 443-5 Extended1)

4

• 2 x 4 CP 443-5 Extended1)

4

 

1) Up to 5 CPs can be plugged into the UR2 rack with a single power

1) Up to 5 CPs can be plugged in per subsystem with a single power

 

supply, or up to 3 with a redundant power supply.

supply, or up to 3 with a redundant power supply.

10/28

Siemens ST PCS 7 · Update November 2008

Page 208
Image 208
Siemens ST PCS 7 manual 10/28, AS 417F Single Station 6ES7 AS 412FH Redundant Station