© Siemens AG 2007

Process I/O

ET 200iSP distributed I/O

Electronics modules and watchdog module

 

 

 

 

 

 

 

 

 

Selection and Ordering Data

Order No.

 

Selection and Ordering Data

Order No.

 

 

Analog electronics modules

 

 

 

 

Analog output modules

 

 

 

Analog input modules

 

 

 

 

 

 

 

 

 

 

 

 

4 AO I HART

6ES7 135-7TD00-0AB0

B)

 

4 AI I 2 WIRE HART

6ES7 134-7TD00-0AB0

B)

 

 

For output of currents to field

 

 

 

 

 

 

 

 

devices with/without HART func-

 

 

 

For measuring currents with

 

 

 

 

 

 

 

 

 

 

 

tionality

 

 

 

2-wire transmitters with/without

 

 

 

 

 

 

 

 

 

 

 

• 4 x 0/4 ... 20 mA, HART

 

 

 

HART functionality

 

 

 

 

 

 

 

• 4 x 4 ... 20 mA, HART, 2-wire

 

 

 

 

(max. load 750 )

 

 

 

 

 

 

 

• Resolution 14 bit

 

 

 

transmitter

 

 

 

 

 

 

 

• Transmitter load: max. 750

 

 

 

 

Short-circuit monitoring

 

 

 

• Resolution 12 bit + sign

 

 

 

 

• Wire break monitoring

 

 

 

Short-circuit monitoring

 

 

 

 

• Parameterizable substitute val-

 

 

 

• Wire break monitoring

 

 

 

 

ue in case of CPU failure

 

 

 

 

 

 

 

 

Watchdog module

6ES7 138-7BB00-0AB0

B)

 

4 AI I 4 WIRE HART

6ES7 134-7TD50-0AB0

 

 

 

 

 

For failure monitoring and for the

 

 

 

For measuring currents with

 

 

 

 

 

 

 

 

 

 

 

intrinsically-safe power supply of

 

 

 

4-wire transmitters with/without

 

 

 

 

 

 

 

 

 

 

 

an external actuator switch-off

 

 

 

HART functionality

 

 

 

 

 

 

 

• 4 x 0/4 ... 20 mA, HART, 4-wire

 

 

 

 

Terminal modules

 

 

 

 

 

 

 

 

 

 

 

transmitter

 

 

 

 

 

 

 

 

 

 

 

 

TM-EM/EM60S terminal module

6ES7 193-7CA00-0AA0

B)

 

• Transmitter load: max. 750

 

 

 

 

for ET 200iSP

 

 

 

• Resolution 12 bit + sign

 

 

 

 

For two electronics modules,

 

 

 

 

 

 

 

screw terminals

 

 

 

• Wire break monitoring

 

 

 

 

 

 

 

 

 

 

 

TM-EM/EM60C terminal module

6ES7 193-7CA10-0AA0

B)

 

 

 

 

 

 

 

4 AI RTD

6ES7 134-7SD50-0AB0

 

 

 

for ET 200iSP

 

 

 

For measuring resistances as well

 

 

 

 

For two electronics modules,

 

 

 

as for temperature measurements

 

 

 

 

spring-loaded terminals

 

 

 

with resistance thermometers

 

 

 

 

 

 

 

 

 

 

 

 

Accessories

 

 

 

• 4 x RTD, resistance thermometer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Reserve module

6ES7 138-7AA00-0AA0

B)

 

Pt100/Ni100

 

 

 

 

 

2-, 3-, 4-wire

 

 

 

 

For any electronics module

 

 

 

 

 

 

 

 

 

 

Resolution 15 bit + sign

Short-circuit monitoring

Wire break monitoring

S7-300 rail

 

• 585 mm long, suitable for

6ES7 390-1AF85-0AA0

assembly of ET 200iSP in a

 

650-mm wide wall housing

 

4 AI TC

6ES7 134-7SD00-0AB0

• 885 mm long, suitable for

6ES7 390-1AJ85-0AA0

For measuring thermal e.m.f. as

 

 

assembly of ET 200iSP in a

 

well as for temperature measure-

 

 

 

950-mm wide wall housing

 

ments with thermocouples

 

 

 

 

 

 

• 4 x TC (thermocouples)

 

• Type B [PtRh-PtRh]

 

• Type N [NiCrSi-NiSi]

11

• Type E [NiCr-CuNi]

 

• Type R [PtRh-Pt]

• Type S [PtPh-Pt]

• Type J [Fe-CuNi]

• Type L [Fe-CuNi]

• Type T [Cu-CuNi]

• Type K [NiCr-Ni]

• Type U [Cu-CuNi]

• Resolution 15 bit + sign

• Internal temperature compensa- tion possible using TC sensor module (included in scope of delivery of module)

• External temperature compen- sation via PT100 connected to RTD module of same ET 200iSP station

• Wire break monitoring

B) Subject to export regulations: AL: N, ECCN: EAR99H

For further accessories such as labeling strips or plates, see Catalog IK PI or the A&D Mall/CA 01 under "ET 200iSP distributed I/O".

11/36

Siemens ST PCS 7 · November 2007

Page 250
Image 250
Siemens ST PCS 7 manual 11/36, Analog electronics modules, Terminal modules