Communication

PROFIBUS PA

Active field distributor AFD and active field splitter AFS

Overview

Active field distributor AFD and active field splitter AFS

Diagnostic displays

Status PA main line PA1, PA2

 

(green)

 

Fault PA main line PA1, PA2 (red)

 

Status/fault PA spur line X1 to X4

 

(green)

Permissible operating temperature

-25 ... +70 °C

Dimensions (W x H x D) in mm

 

120 x 57 x 80

Weight

Approx. 700 g

 

 

Active field splitter AFS

 

Active field distributor AFD

An active field distributor (AFD) can integrate up to

4PROFIBUS PA field devices via short-circuit proof spur line connections into a PROFIBUS PA ring with automatic bus termi- nation. The PROFIBUS PA ring is connected to two FDC 157-0 DP/PA couplers of a DP/PA router. Up to 8 AFDs and up to

31PROFIBUS PA devices can be configured per ring. The num- ber of PROFIBUS PA devices is additionally limited by the max. current consumption of 1 A for all devices.

Connection of PROFIBUS PA field devices

Power supply

Current consumption

Power loss

Output voltage for PA section

Voltage failure bridging

Output current for PA section (for dimensioning of device configura- tion)

Diagnostic displays

Max. 31 per line

Operating environment up to zone 2 or 22

Max. current consumption of all devices 1 A

16 V DC (16 ... 32 V)

Approx. 20 mA

Approx. 600 mW

31 V ± 1 V DC

5ms

1A

Status PA main line PA1, PA2 (green)

Fault PA main line PA1, PA2 (red)

An AFD can be replaced during operation. The function of the PROFIBUS PA devices on the other AFDs is not influenced by this.

Active field splitter AFS

The active field splitter (AFS) connects a PROFIBUS PA line with two redundant FDC 157-0 DP/PA couplers of a DP/PA router. The AFS switches the PROFIBUS PA line to the active one of the two redundant couplers.

Up to 31 PROFIBUS PA devices can be connected on the PROFIBUS PA line. This number is additionally limited by the max. current consumption of 1 A for all devices.

Technical specifications

Active field distributor AFD and active field splitter AFS

 

 

Permissible operating temperature

-25 ... +70 °C

 

 

 

 

 

 

 

 

 

 

Dimensions (W x H x D) in mm

120 x 57 x 80

 

 

 

9

 

 

Weight

Approx. 700 g

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Selection and Ordering Data

Order No.

 

 

 

 

 

 

 

 

 

 

 

Active field distributor AFD

6ES7 157-0AF81-0XA0

B)

 

 

 

 

with 4 short-circuit-proof spur line

 

 

 

 

 

 

connections for integration of field

 

 

 

 

 

 

devices

 

 

 

 

 

 

 

Active field splitter AFS

6ES7 157-0AF82-0XA0

B)

 

 

 

for connecting a PROFIBUS PA

 

 

 

 

 

 

 

line to 2 redundant FDC 157-0

 

 

 

 

 

 

 

DP/PA couplers; automatic

 

 

 

 

 

 

 

switchover to the active coupler

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Profile rail adapter

6ES7 157-0AF83-0XA0

 

 

 

 

 

 

for an active field distributor AFD

 

 

 

 

 

Active field distributor AFD

Connection of PROFIBUS PA field devices

Current Imax. per spur line X1 to X4

Power supply

Current consumption

Power loss

Output voltage for PA section

Voltage failure bridging

Output current for PA section (for dimensioning of device configura- tion)

Max. 4 per AFD

Max. 31 per ring

Operating environment up to zone 2 or 22

Max. current consumption of all devices 1 A

60 mA

16 V DC (16 ... 32 V)

Approx. 20 mA

Approx. 600 mW 31 V ± 1 V DC

5ms

1A

or active field splitter AFS,

optional

B) Subject to export regulations: AL: N, ECCN: EAR99H

Siemens ST PCS 7 · November 2007

9/49

Page 177