© Siemens AG 2007

Communication

PROFIBUS DP

 

 

 

 

 

AS connection

 

 

 

 

 

 

 

Overview

Selection and Ordering Data

Order No.

 

 

 

 

CP 443-5 Extended

6GK7 443-5DX04-0XE0

 

 

 

 

 

 

Communications processor for

 

 

 

 

 

 

 

connection of SIMATIC S7-400 to

 

 

 

 

 

 

 

PROFIBUS as DP master or for S7

 

 

 

 

 

 

 

communication,

 

 

 

 

 

 

 

for data set routing of SIMATIC

 

 

 

 

 

 

 

PDM

 

 

 

 

 

 

 

IF 964-DP

6ES7 964-2AA04-0AB0

 

 

 

 

 

 

Interface module for connection

 

 

 

 

 

 

 

of another PROFIBUS DP line, for

 

 

 

 

 

 

 

plugging into a free DP module

 

 

 

 

 

 

 

slot of the CPU

 

 

 

 

 

 

 

 

 

 

 

PROFIBUS DP lines can be connected to a SIMATIC PCS 7 au- tomation system (controller) via up to 4 internal interfaces in the CPU and up to 10 additional CP 443-5 Extended communica- tions processors.

If a module slot provided in the CPU for the PROFIBUS connec- tion is still vacant, an IF 964-DP interface module is required in addition. When using data set routing with SIMATIC PDM, use of the CP 443-5 Extended communications processor is essential for the PROFIBUS connection.

Benefits

 

Advantages of the CP 443-5 Extended communications module:

9

• Compact design; 9-contact Sub-D socket for connection to

PROFIBUS DP

• Simple installation

Can be plugged into AS rack slot; connection to the other S7-400 modules via backplane bus

• Operation without fan; backup battery or memory submodule are not required