© Siemens AG 2007

 

 

 

 

 

Process I/O

 

 

 

 

ET 200iSP distributed I/O

 

 

 

 

 

RS 485-IS coupler

 

 

 

 

 

 

 

Overview

Selection and Ordering Data

Order No.

 

 

 

 

RS 485-IS coupler

6ES7 972-0AC80-0XA0

 

 

 

 

 

Isolating transformer for connec-

 

 

 

tion of PROFIBUS DP segments with RS 485 and RS 485-iS trans- mission technologies

Tasks of the RS 485-iS coupler

Conversion of the electrical PROFIBUS DP RS 485 transmis- sion technology into the intrinsically-safe RS 485-iS transmis- sion technology with a transmission rate of 1.5 Mbit/s

Required to connect intrinsically-safe PROFIBUS DP stations, e.g. ET 200iSP, ET 200iS or devices from other vendors with Ex i DP connection

Functionality as a safety barrier

Additional use as a repeater in the hazardous area

Passive bus station (no configuration necessary)

Certified according to ATEX 100a

Design

The RS 485-iS coupler is an open unit; assembly is only per- missible in housings, cabinets or rooms for electrical equip- ment.

The RS 485-iS coupler is approved for use in hazardous areas of zone 2.

It must be fitted in a housing which at least corresponds to the IP54 degree of protection. A manufacturer’s declaration for zone 2 (according to EN 50021) is required for the housing and the necessary cable glands.

The RS 485-iS coupler can be used in a horizontal or vertical position.

Installation is on a SIMATIC S7-300 rail.

Diagnostics LEDs on the front panel signal the operating sta- tus.

Connection to PROFIBUS DP

Connection to standard PROFIBUS DP via standard Sub-D socket (at the bottom on the RS 485-iS coupler, behind the right front door).

Integral bus connection for PROFIBUS DP with RS 485-iS transmission technology

Connection of PROFIBUS DP with RS 485-iS transmission technology via screw terminals (at the top of the RS 485-iS coupler, behind the right front door)

The last bus station on the intrinsically-safe PROFIBUS DP segment (not further RS 485-iS couplers) must be terminated by a selectable resistance using the connector, Order No. 6ES7 972-0DA60-0XA0.

Accessories

 

 

PROFIBUS connector with

6ES7 972-0DA60-0XA0

B)

selectable terminating resistor

 

 

For connection of IM 152 to

 

 

PROFIBUS DP with RS 485-iS

 

 

transmission technology

 

 

S7-300 rails

 

 

Lengths:

 

 

• 160 mm

6ES7 390-1AB60-0AA0

 

 

• 482 mm

6ES7 390-1AE80-0AA0

 

• 530 mm

6ES7 390-1AF30-0AA0

 

• 830 mm

6ES7 390-1AJ30-0AA0

 

• 2000 mm

6ES7 390-1BC00-0AA0

 

PROFIBUS Fast Connect bus

6XV1 830-0EH10

 

cable

 

 

Standard type with special design

 

 

for fast mounting, 2-core,

 

 

shielded, cut-to-length; max.

 

 

delivery unit 1000 m, minimum

 

 

ordering quantity 20 m

 

 

 

 

 

B) Subject to export regulations: AL: N, ECCN: EAR99H

11

Siemens ST PCS 7 · November 2007

11/37

Page 251
Image 251