Function

WinAC Slot 416 V4.0

Through use of the WinAC Slot 416 V4.0, it is possible for the au- tomation program in the Slot CPU to execute completely auton- omously from the SIMATIC Box PC and its Windows operating system. Therefore the system can be restarted even if the SIMATIC Box PC is switched off or faulty. 24 V DC from a sepa- rate source is connected to the Slot CPU to provide a power sup- ply independent of the PC. Neither software faults on the PC side, nor a power loss, nor rebooting of the PC have an effect on execution of the automation program in the Slot CPU.

If one of the following events occurs, the automation program is immediately informed and can thus react accordingly, e.g. by in- termediate storage of production data and transfer of the system to a defined status:

Shutting-down of the Windows operating system

Fault in the Windows operating system ("blue screen")

Failure of PC-internal communication

Switching-off of the PC (Separate 24 V DC supply required)

With the SIMATIC PCS 7 BOX 416, the process I/O is connected via the two PROFIBUS DP ports of the WinAC Slot 416 V4.0. In conjunction with SIMATIC PCS 7 V7.0, the WinAC Slot 416 V4.0 also permits changes to the configuration during operation (CiR). The type and scope of online modifications depend on the process I/O used.

Since SIMATIC PDM can only access field devices on the PROFIBUS DP via the onboard CP 5611 communications pro- cessor, an additional link is required between the DP port and the CP 5611. The plug required belongs to the scope of delivery of the SIMATIC PCS 7 BOX 416.

Use with SIMATIC BATCH

SIMATIC PCS 7 BOX 416 systems can also be used for automa- tion of batch processes with SIMATIC BATCH. The capacity of SIMATIC BATCH is limited to 10 UNITs (instances of plant units) in this case. The following SIMATIC BATCH option packages can be executed on the SIMATIC PCS 7 BOX in addition to the SI- MATIC BATCH Server Basic Package for up to 10 UNITs:

Batch Control Center

Recipe System

Batch Planning

Hierarchical Recipe

ROP Library

Separation Procedures/Formulas

Use with SIMATIC Route Control

SIMATIC PCS 7 BOX 416 systems are not only suitable for auto- mation of batch processes with SIMATIC BATCH, but also for control of material transports with SIMATIC Route Control. The capacity of SIMATIC Route Control is limited to 30 simultaneous material transports in this case. The SIMATIC Route Control Server and SIMATIC Route Control Center runtime software is then executed on the SIMATIC PCS 7 BOX 416. The Route Con- trol Engineering is also possible on a SIMATIC PCS 7 BOX 416 all-in-one system.

Technical specifications

Basic hardware: SIMATIC Box PC 627B

 

 

3

Design and equipment features

 

Design

Rack-mountable device with rug-

 

 

ged metal enclosure, suitable for

 

 

wall and portrait mounting

 

Degree of protection to EN 60529

IP20

 

CPU

 

 

• Processor

Intel Core 2 Duo T7400 2.16 GHz

 

• Front Side Bus

667 MHz

 

• Second Level Cache

 

 

4 MB

 

Chipset

Intel 945 GM

 

Main memory

2 GB DDR2-667 SDRAM

 

 

(2 x 1 GB)

 

Graphics

 

 

• Graphics controller

Intel 2D/3D GMA950, integrated

 

 

in chipset

 

• Graphics memory

Dynamic video memory 8 to

 

 

128 MB

 

• Resolutions/colors/frequencies

• VGA: Max. 1600 x 1200 /

 

 

32 bit colors / 85 Hz

 

 

• DVI: Max. 1600 x 1200 /

 

 

32 bit colors / 60 Hz

 

Drives

 

 

• Flash drive

For CompactFlash card

 

• Hard disk

3.5" SATA, 160 GB

 

• Optical drive

DVD ± R/RW

 

• Diskette drive

Connectable via USB (not

 

 

included in scope of delivery)

 

Interfaces

 

 

 

 

 

• PROFIBUS/MPI

1 x 9-contact Sub-D socket,

 

 

12 Mbit/s (electrically isolated,

 

 

CP 5611-compatible)

 

• Ethernet

2 x 10/100/1000 Mbit/s (RJ 45)

 

• USB

4 x USB 2.0/high-speed

 

 

(2 x high-current)

 

• Serial

1 x COM1 (V.24), 9-contact

 

 

Sub-D connector

 

• Parallel

-

 

• Graphics connection

1 x DVI-I (DVI/VGA combined):

 

 

• DVI: digital

 

 

• VGA analog

 

• Keyboard/mouse

Connectable via USB (keyboard

 

 

not included in scope of deliv-

 

 

ery)

 

Operating system and

 

 

diagnostics software

 

 

Operating system

Windows XP Professional MUI

 

 

preinstalled on hard disk and

 

 

enclosed on restore DVD, no

 

 

activation necessary

 

System-tested SIMATIC industrial

SIMATIC PC DiagMonitor

 

software

 

 

 

 

 

Siemens ST PCS 7 · November 2007

3/9

Page 41
Image 41