© Siemens AG 2007

Process I/O

ET 200S distributed I/O

SIGUARD safety technology

 

 

 

Overview

Design

Components required for applications with safety require- ments

Components required

Safety category acc. to EN 954-1

 

 

2

3

 

4

PM-D F1...5

 

1)

TM-PF30 S47-..

 

F-Kit 1/2

2)

2)

 

2)

PM-X

 

TM-X15 S27-01

 

Redundantly

 

 

switching, external

 

 

 

 

infeed contactor

 

 

 

 

 

 

 

 

 

1) PM-D F3 power module only approved up to Category 3

2) F kit required for standard motor starter only; already integrated in high feature motor starter

The SIGUARD safety system is based on special terminal and power modules that can be combined with the ET 200S motor starters and a failsafe kit to achieve the highest safety category

4(according to EN 954-1). It enables the evaluation of emer- gency stop circuits, the monitoring of protective doors or the im- plementation of time-delayed shut-downs. The costs involved in the configuration and wiring of conventional safety systems are no longer incurred. All standard safety applications can be cov- ered with SIGUARD (see the ET 200S manual for examples of applications).

Possible combinations of power and terminal modules

 

PM-D PM-D PM-D PM-D PM-D PM-X

 

F1

F2

F3

F4

F5

TM-PF30 S47-B1 1)

 

 

 

TM-PF30 S47-B0 2)

 

 

 

TM-PF30 S47-C1 3)

 

 

 

TM-PF30 S47-C0 4)

 

 

 

TM-PF30 S47-D0

 

 

 

 

TM-X15 S27-01

 

 

 

 

1)For F1 or F2 in higher-level or individual safety group (voltage group)

2)For F1 or F2 in lower-level cascaded safety group (partial voltage group)

3)For expansion with F3 or F4 in separate ET 200S station (voltage group)

4)For expansion with F3 or F4 in the same ET 200S station (partial voltage group)

11

Siemens ST PCS 7 · November 2007

11/53

Page 267
Image 267