Siemens ST PCS 7 manual AI analog input modules, 11/19

Models: ST PCS 7

1 344
Download 344 pages 20.13 Kb
Page 233
Image 233

 

 

© Siemens AG 2007

 

 

 

 

 

 

Process I/O

 

 

 

 

 

 

ET 200M distributed I/O

 

 

 

 

 

 

AI - analog input modules

 

 

 

 

 

 

 

 

Overview

 

Selection and Ordering Data Order No.

 

The analog input modules described here break down into

multi-function modules for current, voltage and temperature measurements, and

special, highly accurate modules for current and voltage mea- surements or temperature measurements.

All modules automatically supply channel-specific and module- internal diagnostics data, except module 6ES7 331-1KF01- 0AB0. With the latter module, channel failure is identified by the PCS 7 analog driver block.

The individual channels of the analog input modules can be pa- rameterized in groups independently of each other.

SM 331 modules for current, voltage and temperature measure- ments

8 inputs, individually parame-

6ES7 331-1KF01-0AB0

terizable

 

Resolution 12 bit + sign

Current measurement 0/4 to

20 mA (8 channels; 2 wires with external supply or 4 wires)

Voltage measurement (8 channels)

Resistance thermometer Pt100, Ni100, Ni1000, LG-Ni1000

(8 channels; 2, 3 or 4 wires)

Front connector required: 40-contact

8 inputs in 4 channel groups

6ES7 331-7KF02-0AB0

Redundant design possible

 

(module redundancy)

 

Changeover of measurement type by range module per chan- nel group

Resolution 14 bit + sign

Current measurement 0/4 to

20 mA (8 channels; 2 or 4 wires)

Voltage measurement (8 channels)

Resistance thermometer Pt100, Ni100 (4 channels, 2 or 4 wires)

Thermocouples type E, N, J, K, L (8 channels),

internal compensation or exter- nal compensation with compen- sating box or 0 °C cold junction

Wire break monitoring

Diagnostics inside module

Front connector required: 20-contact

2 inputs in 1 channel group

6ES7 331-7KB02-0AB0

B)

 

• Changeover of measurement

 

 

 

 

 

 

 

 

type by range module

 

 

 

 

• Resolution 14 bit + sign

 

 

 

11

• Current measurement 0/4 to

 

 

 

 

20 mA (2 channels; 2 or 4 wires)

 

 

 

 

• Voltage measurement

 

 

 

 

(2 channels)

 

 

 

 

• Resistance thermometer Pt100,

 

 

 

 

Ni100 (1 channel, 2 or 4 wires)

 

 

 

 

• Thermocouples type E, N, J, K, L

 

 

 

 

(2 channels),

 

 

 

 

internal compensation or exter-

 

 

 

 

nal compensation with compen-

 

 

 

 

sating box or 0 °C cold junction

 

 

 

 

• Wire break monitoring

 

 

 

 

• Diagnostics inside module

 

 

 

 

• Front connector required:

 

 

 

 

20-contact

 

 

 

 

B) Subject to export regulations: AL: N, ECCN: EAR99H

Siemens ST PCS 7 · November 2007

11/19