© Siemens AG 2007

Communication

Industrial Ethernet

OSM/ESM/OMC Industrial Ethernet switches

 

 

The transmission rate in the ring is 100 Mbit/s; for each ring, up

Overview

 

to 50 Industrial Ethernet OSMs (optical ring) or ESMs (electrical

 

 

ring) can be used. Apart from the 2 ring ports, OSM/ESM has

 

 

other ports (with either RJ45, ITP or BFOC interfaces) to which

 

 

data terminals or network segments can be connected.

 

 

Selection support for the various product versions of OSM is pro-

 

 

vided by the table under "Technical specifications".

 

 

Industrial Ethernet media converter

 

 

Industrial Ethernet nodes with RJ45 TP interface can be con-

 

 

nected via an Industrial Ethernet media converter to one of the

 

 

8 optical ports of an OSM BC08. The two types of media con-

 

 

verter SCALANCE X101-1 or X101-1LD convert the electric

 

 

twisted-pair interface, port type 10/100BaseTX (10/100 Mbit/s,

 

 

RJ45 socket) as follows:

 

 

X101-1: into an optical interface for multimode glass FOC

 

 

X101-1LD: into an optical interface for singlemode glass FOC

 

 

The port type of the optical interface is 100BaseFX in each case

 

 

(100 Mbit/s; 2 x BFOC socket).

 

 

Notes:

 

 

Just like the OMC TP11 media converter, the SCALANCE X101-1 does

 

 

not support diagnostics per SNMP protocol.

 

 

For further information on the Industrial Ethernet media converter, see

 

 

Catalog IK PI, Section "Active network components - Industrial Ethernet

 

 

media converter".

The Industrial Ethernet OSM and ESM switches are used to con-

 

Technical specifications

struct Industrial Ethernet networks at the control level:

 

 

The modules are interconnected (backbone) at 100 Mbit/s over

-Glass fiber-optic cables (FO) for OSM

-Twisted pair cables for ESM

Connection of data terminals or network segments depending on the OSM/ESM type through

-2 to 8 twisted pair ports 10/100BaseTX in RJ45 or 9-pole Sub-D design for 10/100 Mbit/s

-3 or 8 FO ports 100BaseFX with BFOC interface (ST socket) for 100 Mbit/s

Integral redundancy manager supports high-speed media re- dundancy also for large networks

Very easy network configuration and extension without com- plex configuration rules or parameterization

Application

Industrial Ethernet OSM and ESM

The Industrial Ethernet OSM (Optical Switch Module) and ESM (Electrical Switch Module) are used in the construction of switched networks with data transmission rates of 100 Mbit/s in the control level range, in which strict demands are placed on network availability and comprehensive diagnostics are re- quired.

In existing networks, load decoupling and thus increased net- work performance can be achieved by creating segments (di- viding a network into subnetworks/segments) and connecting these segments to an OSM/ESM.

The redundancy manager integrated into OSM/ESM allows In- dustrial Ethernet rings to be constructed in switching technology with high-speed switching over of the communication path on failure of a switch or interruption in the transmission path (recon- figuration time max. 0.3 seconds).

Selection support for product versions of OSM and ESM

 

 

 

Type and

 

Preferentially

 

 

 

 

 

 

 

 

 

 

number of ports

 

 

for use

 

 

9

 

RJ45(TP)

 

(ITP)D-Sub

modeMulti-FO

modeSingle- FO

With

For

For ter-

 

 

 

high

plant

minal

 

 

 

 

 

 

 

EMC

bus

bus

 

 

 

 

 

 

 

loading

 

(OS-

 

 

 

 

 

 

 

 

 

LAN)

 

 

 

 

 

 

 

 

 

 

 

 

OSM TP22

2

 

2

n 1)

n

n

 

 

OSM ITP62

 

6

2

n

n

n

 

(Standard)

 

 

 

 

 

 

 

 

 

 

OSM TP62

6

 

2

 

n

n

 

 

OSM ITP62-LD

 

6

2

n

n

n

 

 

OSM ITP53

 

5

3

n

n 2)

n 2)

 

 

OSM BC08

 

–-

8

n 3)

n 3)

n 3)

 

 

SCALANCE

1

 

–-

1

n 4)

n 4)

n 4)

 

X101-1

 

 

 

 

 

 

 

 

 

 

SCALANCE

1

 

–-

–-

1

n 4)

n 4)

n 4)

 

 

X101-1LD

 

 

 

 

 

 

 

 

 

 

ESM ITP80

 

8

n

n 5)

n

 

 

ESM TP40

4

 

 

n 6)

n

 

ESM TP80

8

 

 

n 6)

n

 

1)TP cable preferably inside a control cabinet

2)For cross-building connection of Fast Ethernet networks with OSM

3)For design of an optical network, where TP cables are preferably only used inside control cabinets

4)Connects a station with RJ45-TP interface to one of the 8 optical ports of an OSM BC08

5)Inside buildings

6)Inside switchrooms

Siemens ST PCS 7 · November 2007

9/21

Page 149
Image 149
Siemens ST PCS 7 manual OSM/ESM/OMC Industrial Ethernet switches, Industrial Ethernet media converter