Siemens ST PCS 7 manual 11/26, Isolating module, SM 336F failsafe analog input module

Models: ST PCS 7

1 344
Download 344 pages 20.13 Kb
Page 240
Image 240

© Siemens AG 2007

Process I/O

ET 200M distributed I/O

F modules

Selection and Ordering Data Order No.

SM 326F failsafe digital output,

suitable for solenoid valves, DC contactors and signal lamps

10 outputs, 24 V DC, 2 A6ES7 326-2BF01-0AB0

Options

Isolating

module F-modules

Electrically isolated in groups of 5 (outputs with internal diode) Redundant design possible (module and channel redun- dancy)

SIL 2, SIL 3 parameterizable (10 channels)

P/P-switching (for non-floating loads; ground and earth con- nected together)

Wire break and short-circuit monitoring

Diagnostics inside module

PROFIsafe telegram

Front connector required: 40-contact

IM 153-2

PROFIBUS copper connection

IM 153-2

ET 200 rack

only for SIL 3 operation, SIL 2 also possible without isolating module

Isolating bus submodule for active

backplane bus

ET 200 rack

 

 

8 outputs, 24 V DC, 2 A

6ES7 326-2BF40-0AB0

 

 

Electrically isolated in groups of 4

 

 

 

• SIL 2, SIL 3 parameterizable

 

 

 

(8 channels)

 

 

 

P/M-switching (for floating

 

 

 

loads; ground and earth sepa-

 

 

 

rate)

 

 

 

• Wire break and short-circuit

 

 

 

monitoring

 

 

 

• Diagnostics inside module

 

 

 

• PROFIsafe telegram

 

 

 

• Front connector required:

 

 

 

40-contact

 

 

 

SM 336F failsafe analog input module

 

 

6 inputs, 4 to 20 mA

 

 

 

6ES7 336-1HE00-0AB0

 

 

Redundant design possible

 

 

 

(module redundancy)

 

 

 

• Resolution 13 bit + sign

 

 

 

• Isolated from the backplane bus

 

 

 

2-wire or 4-wire connection

 

 

 

• SIL 2: two-channel evaluation,

 

11

 

6 sensors

 

 

 

• SIL 3: two-channel evaluation,

 

 

 

12 sensors (adjustable toler-

 

 

 

 

 

ance window)

 

 

 

• Wire break monitoring

 

 

 

• Tolerance monitoring between

 

 

 

2 sensors (SIL 3)

 

 

 

• Diagnostics inside module

 

 

 

• PROFIsafe telegram

 

 

 

• Front connector required:

 

 

 

40-contact

 

 

 

Options

 

 

 

Isolating module

 

 

 

6ES7 195-7KF00-0XA0

 

 

For F modules, 40 mm wide

 

 

 

• For isolation of F and standard

 

 

 

modules in an ET 200M rack

 

 

 

• For signal isolation when using a

 

 

 

copper bus connection (only F

 

 

 

modules in a rack with IM 153-2)

 

 

 

Isolating bus module

6ES7 195-7HG00-0XA0

 

 

80 mm wide, for isolating module,

 

 

 

when using an active backplane

 

 

 

bus

 

 

 

 

 

PROFIBUS

Isolating module for isolation of

copper connection

standard and F-modules

or fiber-optic cable

 

Isolating module

The following components are available as accessories for the F modules:

Isolating module

-For isolation of F and standard modules in an ET 200M re- mote I/O station

-For signal isolation when using a copper bus connection (only F modules in an ET 200M remote I/O station with IM 153-2)

Isolating bus submodule for isolating module, when using an active backplane bus

Note:

The isolating module for F modules and the isolating bus sub- module can only be used together. The 40-mm wide gap cannot be used for other modules.