© Siemens AG 2007

Process I/O

ET 200M distributed I/O

Ex modules [EEi xb]

 

 

 

 

 

Overview

Selection and Ordering Data

Order No.

 

 

 

4 outputs, 15 V DC / 20 mA in

6ES7 322-5RD00-0AB0

 

 

 

4 channel groups

 

 

 

 

• Individually floating channels

 

 

 

 

• Wire break monitoring

 

 

 

 

Short-circuit monitoring

 

 

 

 

• Diagnostics inside module

 

 

 

 

• Front connector required:

 

 

 

 

20-contact

 

 

 

 

Ex analog input module

 

The following analog and digital I/O modules are suitable for use in hazardous plants. They separate the non-intrinsically safe electrical circuits of the automation system and the intrinsically safe electrical circuits of the process. Sensors and actuators suitable for placing in zone 1 or 21 and 2 or 22 hazardous areas as well as intrinsically safe equipment compliant with DIN 50020 and [EEx ib] IIC can be operated on these modules.

All Ex modules come with diagnostics capability (channel and module diagnostics).

Ex modules identified by "redundant design possible"

(6ES7 321-7RD00-0AB0, 6ES7 322-5SD00-0AB0, 6ES7 331- 7RD00-0AB0, 6ES7 332-5RD00-0AB0) can also be configured redundant when used in non-hazardous plants.

 

 

Selection and Ordering Data

Order No.

 

 

 

Ex digital input module

 

 

 

 

 

 

 

 

 

4 NAMUR inputs in 4 channel

6ES7 321-7RD00-0AB0

 

 

 

groups

 

 

 

 

Redundant design possible

 

 

 

 

 

 

(module redundancy)

 

11

 

 

• Voltage supply to sensors 8.2 V

 

 

 

 

• Individually floating channels

 

 

 

 

• Wire break and short-circuit

 

 

 

 

monitoring (directly at the con-

 

 

 

 

tact for contacts with external

 

 

 

 

resistor circuit)

 

 

 

 

• Diagnostics inside module

 

 

 

 

• Front connector required:

 

 

 

 

20-contact

 

 

 

 

Ex digital output module

 

 

 

 

4 outputs, 24 V DC / 10 mA in

6ES7 322-5SD00-0AB0

 

 

 

4 channel groups

 

Redundant design possible (module redundancy)

• Individually floating channels

• Wire break monitoring

Short-circuit monitoring

• Diagnostics inside module

• Front connector required: 20-contact

4 inputs, 0/4 to 20 mA in

6ES7 331-7RD00-0AB0

4 channel groups

 

Redundant design possible

 

(module redundancy)

 

Individually floating channels

Resolution 15 bit + sign

Connection of 2-wire or 4-wire transmitters possible

Wire break monitoring

Measurement range monitoring

Short-circuit-proof

Diagnostics inside module

Front connector required: 20-contact

8 inputs in 4 channel groups

6ES7 331-7SF00-0AB0

Resolution 15 bit + sign

Thermocouples type T, U, E, J, L, K, N, R, S, B (8 channels) Internal compensation; external compensation with Pt100

(2 channels), compensating box or 0/50 °C cold junction

Resistance thermometer Pt100, Pt200, Ni100 (4 channels; 2-wire or 4-wire, 3-wire Pt100 on request)

Wire break monitoring

Diagnostics inside module

Front connector required: 20-contact

Note:

A special front connector for the Ex analog input module 6ES7

331-7SF00-0AB0 enables greater accuracy when taking thermo- couple temperature measure- ments in "internal compensation" mode (see page 11/12).

Ex analog output module

 

4 outputs, 0/4 to 20 mA in

6ES7 332-5RD00-0AB0

4 channel groups

 

Redundant design possible

 

(module redundancy)

 

Individually floating channels

Resolution 15 bit

For 2-wire transmitters

Wire break monitoring

Diagnostics inside module

Front connector required: 20-contact

For additional Ex modules, refer to page 11/23.

11/22

Siemens ST PCS 7 · November 2007

Page 236