Communication

PROFIBUS DP

Introduction

Application

The PROFIBUS DP fieldbus enables the SIMATIC PCS 7 auto- mation systems (controllers) to communicate with distributed I/Os from the ET 200 range (remote I/Os) as well as with field/process devices, CPUs/CPs and operator terminals that have a PROFIBUS DP interface. It is possible to route the PROFIBUS DP into Ex zone 1 by using a fieldbus isolating trans- former (RS 485-iS coupler) and the RS 485-iS transmission tech- nology. Connection of the intelligent, distributed field/process devices and operator terminals on PROFIBUS PA to the automa- tion system takes place likewise through PROFIBUS DP.

Depending on the type of automation system and the number of available slots, up to 4 PROFIBUS DP lines can be connected to

a SIMATIC PCS 7 automation system through internal interfaces in the CPU, and up to 10 PROFIBUS DP lines through additional CP 443-5 Extended communications processors. On a PROFIBUS DP line it is possible to operate up to 125 devices, and on a bus segment up to 31 devices with PROFIBUS DP in- terface (32 stations).

Electrical and optical transmission technologies offer many dif- ferent configuration options for PROFIBUS DP networks. Electri- cal networks can span up to approx. 10 km. With optical trans- mission systems, the total size of the network is governed primarily by the cycle times as a result of the almost loss-free transmission.

With SIMATIC PCS 7, PROFIBUS DP topologies are always im- plemented through the standard electrical PROFIBUS DP con- nection on the automation system in the form of electrical or mixed (electrical/optical) networks. In the case of mixed net- works, the transition between the two media is implemented by an optical link module (OLM). As regards communication be- tween the stations, there is no difference between electrical two- wire technology and fiber optic technology.

Electrical networks can be configured with a line or tree topol- ogy. Mixed electrical/optical networks with OLMs as routers can be configured with a line, ring or star topology.

Technical specifications

 

 

PROFIBUS DP

 

 

 

 

 

Data transmission

RS 485

RS 485-iS

Fiber-optic

9

 

Transmission rate

9.6 kbit/s ... 12 Mbit/s

9.6 kbit/s ... 1.5 Mbit/s

9.6 kbit/s ... 12 Mbit/s

 

 

 

 

 

 

 

 

 

 

Cable

2-wire shielded

2-wire shielded

Plastic as well as multi-mode and

 

 

 

 

 

single-mode glass-fiber

 

 

 

 

 

 

 

 

Type of protection

 

EEx(ib)

 

 

 

 

 

 

 

 

 

Topology

Line, tree

Line

Ring, star, line

 

 

 

 

 

 

 

 

Nodes per segment

32

32 1)

 

 

Nodes per network (with

126

126

126

 

 

repeater)

 

 

 

Cable length per segment depen- dent on transmission rate

1200 m at max. 93.75 kbit/s

1000 m at 187.5 kbit/s

400 m at 500 kbit/s

200 m at 1.5 Mbit/s

100 m at 12 Mbit/s

1000 m at 187.5 kbit/s1)

Max. 80 m (plastic)

400 m at 500 kbit/s1)

2-3 km (multi-mode glass-fiber)

200 m at 1.5 Mbit/s1)

>15 km at 12 Mbit/s (single-mode

 

glass-fiber)

Repeater for signal refreshing

Max. 9

Max. 91)

Not relevant

with RS 485 networks

 

 

 

1)According to PROFIBUS installation guideline 2.262

9/36