Siemens ST PCS 7 manual 10/5, Design and equipment features

Models: ST PCS 7

1 344
Download 344 pages 20.13 Kb
Page 185
Image 185

© Siemens AG 2008

Automation systems

Microbox automation system

Two Ethernet interfaces 10/100/1000 Mbit/s (RJ45) are inte- grated in the SIMATIC PCS 7 AS RTX for plant bus communica- tion with SIMATIC PCS 7 subsystems such as operator system, engineering system or maintenance station.

ET 200M, ET 200ISP and ET 200S I/O stations can be linked over a PROFIBUS DP interface to a comprehensive range of low- cost signal/function modules as well as intelligent field/process devices on the PROFIBUS PA.

The SIMATIC PCS 7 AS RTX is configured using the central en- gineering system of the SIMATIC PCS 7 process control system.

The engineering system also administers the AS Runtime li- censes of the SIMATIC PCS 7 AS RTX. The scope of delivery of the SIMATIC PCS 7 AS RTX already includes an AS Runtime license for 250 POs. This can be expanded by further AS Run- time licenses for 100 POs. The process objects of additional AS Runtime licenses are then added to process objects which already exist.

Technical specifications

SIMATIC PCS 7 AS RTX

Design and equipment features

Design

DIN rail or wall mounting;

 

horizontal (preferred) or vertical

Degree of protection to EN 60529

IP20

(front/rear)

 

CPU

 

 

• Processor

Intel Pentium M 1.4 GHz

• Front Side Bus

400 MHz

• Second Level Cache

2 MB

Chipset

Intel Alviso 910GML

Main memory

1 GB DDR2-SDRAM (SO-DIMM

 

modules)

Graphics

 

• Graphics controller

Intel 2D/3D GMA900, integrated

 

in chipset

• Graphics memory

Dynamic video memory 8 to

 

128 MB

• Resolutions/colors/frequencies

 

- CRT

Up to 1600 x 1200 / 32 bit colors /

 

60 to 120 Hz

- DVI

Up to 1600 x 1200 / 32 bit colors

Drives

 

• Flash drive

For CompactFlash card, 2 GB

CD-ROM / DVD-RW / diskette

Connectable via USB (not

 

included in scope of delivery)

 

 

Technical specifications

Interfaces

 

 

 

 

• PROFIBUS/MPI

 

12 Mbit/s (electrically isolated,

 

 

 

 

CP 5611-compatible), 9-contact

 

 

 

 

Sub-D socket

 

 

• Ethernet

 

2 x 10/100/1000 Mbit/s (RJ 45),

 

 

 

 

two independent controllers

 

 

• USB

 

4 x USB 2.0/high-speed

 

 

• Serial

 

1 x COM1 (V.24), 9-contact Sub-D

 

 

 

 

connector

 

 

 

 

 

 

 

• Parallel

 

-

 

 

• Graphics connection

 

1 x DVI-I (DVI/VGA combined):

 

 

 

 

• DVI: digital

 

 

 

 

• VGA analog

 

 

• Keyboard/mouse

 

Connectable via USB (not

 

 

 

 

included in scope of delivery)

 

 

LED displays

 

• Power

 

 

 

 

• Watchdog

 

 

Operating system / basic software

 

 

 

 

 

 

Operating system

 

Windows XP Embedded prein-

 

 

 

 

stalled on CompactFlash card

 

 

 

 

(CF card) 2 GB, no activation

 

 

 

 

required

 

 

 

 

 

 

 

System-tested SIMATIC industrial

 

WinAC RTX

 

 

software

 

DiagMonitor

 

 

 

 

 

 

Monitoring/diagnostics functions

 

 

 

 

 

 

Watchdog

 

• Monitoring of program execution

 

 

 

 

• Restart can be parameterized

 

 

 

 

following faults

 

 

 

 

• Monitoring time adjustable in the

 

 

 

 

software

 

 

 

 

 

Temperature

 

• Processor

 

10

 

 

• Motherboard

 

 

 

(via SIMATIC PC DiagMonitor and

 

 

 

 

SIMATIC PCS 7 Asset Manage-

 

 

 

 

ment)

 

 

 

 

 

 

 

Operating hours counter

 

(via SIMATIC PC DiagMonitor and

 

 

 

 

SIMATIC PCS 7 Asset Manage-

 

 

 

 

ment)

 

 

Safety

 

 

 

Protection class

Protection class I compliant with

 

 

 

IEC 61140

 

Safety directives

EN 60950-1; UL 60950;

 

 

 

CAN/CSA-C22.2 No. 60950-1;

 

UL 508; CAN/CSA-C22.2 No. 142 or CAN/CSA-C22.2 No. 14-05

Noise level

Operation

< 40 dB (A) to DIN 45635-1

 

 

Siemens ST PCS 7 · Update November 2008

10/5

Page 185
Image 185
Siemens ST PCS 7 manual 10/5, Design and equipment features