Siemens ST PCS 7 manual Power module PM-E, 11/65, Connection module

Models: ST PCS 7

1 344
Download 344 pages 20.13 Kb
Page 279
Image 279

 

 

© Siemens AG 2007

 

 

 

 

 

 

Process I/O

 

 

 

 

 

 

Dezentrale Peripherie ET 200pro

 

 

 

 

 

 

Power module PM-E

 

 

 

 

 

 

 

 

Overview

 

Selection and Ordering Data Order No.

 

The power module PM-E DC 24 V is used within an ET 200pro station when generating 24 V DC load voltage groups for elec- tronics modules.

You can position power modules in an ET 200pro station any- where to the right of the interface module. The first power mod- ule is already integrated in the interface module.

Each power module which you install in the ET 200pro station in- terrupts the load voltage busbar, and opens up a new potential group (common potential) for the load voltage supply 2L+. All subsequent load voltages of the electronics modules are fed from this power module. Each power module has a replaceable fuse for protecting the device. Only line protection according to DIN VDE 0100 need be provided externally in addition.

Power module

 

 

 

 

 

Power module PM-E DC 24 V

6ES7148-4CA00-0AA0

B)

For generating 24 V DC load volt-

 

 

age groups for electronics mod-

 

 

ules within an ET 200pro station.

 

 

Accessories

 

 

Connection modules for power

 

 

 

 

module

 

 

• Connection module CM PM-E

6ES7 194-4BA00-0AA0

B)

ECOFAST

 

 

for supply of 24 V DC load volt-

 

 

age, 1 ECOFAST Cu connection

 

 

• Connection module CM PM-E

6ES7 194-4BC00-0AA0

B)

direct

 

 

for supply of 24 V DC load volt-

 

 

age, up to two M20 cable

 

 

glands

 

 

• Connection module CM PM-E

6ES7 194-4BD00-0AA0

B)

7/8"

 

 

for supply of 24 V DC load volt-

 

 

age, 1 x 7/8"

 

 

 

 

 

Spare fuse

6ES7 194-4HB00-0AA0

 

12.5A fast-blow, for interface and power modules, 10 units per pack

Further accessories

For plugs, cables and further accessories, see Catalog IK PI or Mall/CA 01 under "Distributed I/O / ET 200pro"

B) Subject to export regulations: AL: N, ECCN: EAR99H

The electronics/sensor supply 1L+ is not interrupted by the power module, it is looped through.

The power module is fitted on the associated bus module when delivered.

Technical specifications

For detailed technical specifications of the power module PM-E, see:

Catalog IK PI

Mall/CA 01 under "Distributed I/Os / ET 200pro"

Accessories

Connection module

The connection module for the power module PM-E is used to connect the load voltage 2L+. It is fitted on the power module.

The module must be ordered separately, and is available with the following types of connection:

• CM PM-E direct

11

• CM PM-E ECOFAST

 

• CM PM-E 7/8"

Siemens ST PCS 7 · November 2007

11/65

Page 279
Image 279
Siemens ST PCS 7 manual Power module PM-E, 11/65, Connection module