© Siemens AG 2007

Process I/O

ET 200M distributed I/O

DO - digital output modules

Selection and Ordering Data Order No.

SM 322 modules with diagnostics capability (with channel and module diagnostics)

for DC voltage (suitable for solenoid valves, DC contactors and indicator lights)

8 outputs, 24 V DC / 0.5 A

6ES7 322-8BF00-0AB0

Redundant design possible

 

(module redundancy)

 

Electrically isolated in groups of 8

2 connections per output (with and without series diode)

Connection of a default value by channel in the event of CPU stop (parameterizable)

Wire break monitoring per chan- nel

Load voltage monitoring per channel

Short-circuit monitoring to M/L+ per channel

Module-internal diagnostics functions

Front connector required: 20-contact

16 outputs, 24 V DC / 0.5 A

6ES7 322-8BH01-0AB0

Redundant design possible

 

(module and channel redun-

 

dancy)

 

Electrically isolated in groups of 4

Connection of a default value by channel in the event of CPU stop (parameterizable)

Wire break monitoring per chan- nel (with 0 and 1 signals)

Signaling of output overload

Load voltage monitoring or ground monitoring per channel group

Short-circuit monitoring to M/L+ per channel group

Module-internal diagnostics functions

Front connector required: 40-contact

Selection and Ordering Data Order No.

for AC voltage (suitable for AC coils, contactors, motor starters, small motors and indicator lights)

8 outputs, 120/230 V AC / 2 A

6ES7 322-5FF00-0AB0

B)

Electrically isolated in groups of 1

Connection of a default value by channel in the event of CPU stop (parameterizable)

Module-internal diagnostics functions

Front connector required: 40-contact

16 outputs, 24/48 V AC/DC /

6ES7 322-5GH00-0AB0

B)

0.5 A

 

 

Electrically isolated in groups of 1

Connection of a default value by channel in the event of CPU stop (parameterizable)

Module-internal diagnostics functions

Front connector required: 40-contact

for relay output (suitable for AC/DC coils, contactors, motor starters, small motors and indicator lights)

8 outputs, 24 to 120 V DC, 24 to

6ES7 322-5HF00-0AB0

B)

230 V AC / max. 5 A

 

 

Electrically isolated in groups of 1

With RC suppressor element for protection of contacts per chan- nel

Connection of a default value by channel in the event of CPU stop (parameterizable)

Module-internal diagnostics functions

Front connector required: 40-contact

B) Subject to export regulations: AL: N, ECCN: EAR99H

11

Siemens ST PCS 7 · November 2007

11/17

Page 231
Image 231
Siemens ST PCS 7 manual 11/17, Outputs, 24 V DC / 0.5 a, Redundant design possible Module and channel redun Dancy