© Siemens AG 2007

Process I/O

ET 200iSP distributed I/O

Introduction

Integration

Distributed ET 200iSP stations are connected to the SIMATIC PCS 7 automation systems (controllers) via the PROFIBUS DP, which can be routed intrinsically-safe into Ex zone 1 using an isolating transformer (RS485-iS coupler) as barrier. Data transfer rates of up to 1.5 Mbit/s are possible.

The modern architecture with independent wiring and automatic slot coding supports simple and reliable hot swapping of individ- ual modules without a fire certificate. To increase plant availabil- ity, both the power supply and the PROFIBUS DP interface can be of redundant design.

The ET 200iSP is integrated into SIMATIC PCS 7 using standard driver blocks. You can therefore configure and parameterize the ET 200iSP in the SIMATIC Manager of the engineering system extremely simply using HW Config. The system function CiR (Configuration in Run) is also supported, and permits the follow- ing changes to be made to the configuration during runtime:

Adding of an ET 200iSP station

Adding of a module in an ET 200iSP station

Reparameterization of modules.

Vendor-specific information and maintenance data are saved powerfail-proof on the electronics modules.

The existing standard diagnostics drivers preprocess the diag- nostics messages generated by internal or external faults (e.g. wire breakage or short-circuit) as well as status messages of the connected HART field devices for the host operator system and the maintenance station of the PCS 7 asset management. The ET 200iSP and the HART field devices can also be parameter- ized using SIMATIC PDM (process device manager). With SI- MATIC PDM you can directly access the HART field devices on the ET 200iSP by routing via PROFIBUS DP.

Technical specifications

Degree of protection

IP30

 

 

 

Ambient temperature

-20 ... +70 °C

 

 

 

Loading of media

According to ISA-S71.04 severity level G1; G2; G3 (except for NH3, only level G2 in this case)

 

 

EMC

Electromagnetic compatibility according to NE21

 

 

Vibration resistance

0.5 g continuously, 1 g occasionally

 

 

 

Approvals, standards

 

 

 

 

• ATEX

 

 

 

II 2 G (1) GD

Ex de [ia/ib] IIC T4

 

 

 

I M2

Ex de [ia/ib] I

 

 

• IECEx

Zone 1

Ex de [ia/ib] IIC T4

 

 

• cFMus

Class I,II,II

NI Division 2, Groups A, B, C, D, E, F, G T4

 

 

 

 

AIS Division 1, Groups A, B, C, D, E, F, G

 

 

 

Class I

Zone 1, AEx de [ia/ib] IIC T4

 

 

 

 

 

 

 

• cULus

Class I,II,II

Division 2, Groups A, B, C, D, E, F, G T4

 

 

 

 

providing int. safe circuits for Division 1, Groups A, B, C, D, E, F, G

 

11

 

Class I

Zone 1, AEx de [ia/ib] IIC T4

 

 

 

 

• PROFIBUS

EN 50170, Volume 2

 

 

 

 

 

 

 

 

• IEC

IEC 61131, Part 2

 

 

 

• CE

According to 94/9/EU (ATEX 100a), 89/336/EEC and 73/23/EEC

 

 

 

 

 

 

 

• Shipbuilding approval

Classification companies

 

 

 

ABS (American Bureau of Shipping)

BV (Bureau Veritas)

DNV (Det Norske Veritas)

GL (Germanischer Lloyd)

LRS (Lloyds Register of Shipping)

Class NK (Nippon Kaiji Kyokai)

For detailed technical specifications, especially on individual components such as power supply module, interface module or electronics modules, see:

Catalog IK PI

Mall/CA 01 under "Distributed I/Os / ET 200iSP"

Siemens ST PCS 7 · November 2007