© Siemens AG 2007

Operator system

OS software

Overview

OS basic hardware and OS software are structured by OS single station, OS server and OS client in compliance with the architec- ture of the operator system and are accordingly coordinated in this regard.

Design

The OS standard software of OS single stations and OS clients can be expanded by SIMATIC PCS 7 SFC Visualization and Safety Matrix Viewer.

The high-performance cyclic buffer archiving system integrated as standard in OS single station and OS server for short-term ar- chiving of up to 512 variables can be expanded within the limit of 10000 variables using SIMATIC PCS 7 archive licenses and SIMATIC PCS 7 Archive PowerPacks. The SIMATIC PCS 7 ar- chive licenses (Count Relevant Licenses) are cumulative. SIMATIC PCS 7 Archive PowerPacks permit expansion in steps from 1500 to 5000 or 10000 variables. For ordering data for SIMATIC PCS 7 Archive and SIMATIC PCS 7 Archive Power- Packs, refer to page 5/20.

The short-term archive can also be combined with a long-term archive. StoragePlus is available for long-term archiving in the bottom performance range, and the central archive server (CAS) is envisaged for the top performance range. See page 5/19 for details.

You can also implement redundant system configurations with OS single stations and OS servers. See page 5/16 for details.

The following tables provide a selection aid for ordering an op- erator station. Depending on whether a redundant or non-redun- dant design is selected, the tables indicate the respectively re- quired number of

SIMATIC PCS 7 Industrial Workstations,

licenses for OS standards software, and

licenses for optionally used supplementary OS software.

 

 

Introduction

 

 

 

 

 

 

 

 

 

 

Single-user system

 

 

 

 

 

 

OS single station

Redundancy

 

 

with Windows XP Professional operating system

 

 

 

 

Without

With

 

 

 

 

SIMATIC PCS 7 Industrial Workstation including

 

 

 

 

 

 

operating system, alternatives

 

 

 

 

 

 

 

 

 

 

 

 

 

SIMATIC PCS 7 ES/OS 547B BCE WXP

1

2

 

 

 

 

with BCE communication for up to 8 automation

 

 

 

 

 

 

systems (not H systems)

 

 

 

 

 

 

SIMATIC PCS 7 ES/OS 547B IE WXP

1

2

 

 

 

 

with Industrial Ethernet communication

 

 

 

 

 

 

 

 

 

 

 

 

Additional IE communications software for

 

 

 

 

5

 

SIMATIC PCS 7 ES/OS 547B IE WXP

 

 

 

 

SIMATIC NET S7-REDCONNECT Upgrade

1

2

 

 

 

 

OS standard software

 

 

 

 

 

 

 

 

 

 

 

 

SIMATIC PCS 7 OS Software Single Station V7.0

 

 

 

 

 

 

1

--

 

 

 

 

SIMATIC PCS 7 Single Station Redundancy V7.0

--

1

 

 

 

 

including RS 232 connecting cable, 10 m

 

 

 

 

 

 

Supplementary OS software (optional)

 

 

 

 

 

 

 

 

 

 

 

 

 

SIMATIC PCS 7 SFC Visualization V7.0

1

2

 

 

 

 

SIMATIC Safety Matrix Viewer for PCS 7

1

2

 

 

 

 

SIMATIC PCS 7 Archive V7.0/ SIMATIC PCS 7

1

2

 

 

 

 

Archive PowerPack for expansion of short-term

 

 

 

 

 

 

cyclic buffer archive

 

 

 

 

 

 

 

 

 

 

 

 

 

Multi-user system with client/server architecture

 

 

 

 

 

 

OS server

Redundancy

 

 

with Windows 2003 Server operating system

 

 

 

 

 

 

Without

With

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SIMATIC PCS 7 Industrial Workstation including

 

 

 

 

 

 

operating system, alternatives

 

 

 

 

 

 

 

 

 

 

 

 

 

SIMATIC PCS 7 OS Server 547B BCE SRV03

1

2

 

 

 

 

with BCE communication for up to 8 automation

 

 

 

 

 

 

systems (not H systems)

 

 

 

 

 

 

SIMATIC PCS 7 OS Server 547B IE SRV03

1

2

 

 

 

 

with Industrial Ethernet communication

 

 

 

 

 

 

 

 

 

 

 

 

Additional IE communications software for

SIMATIC PCS 7 OS Server 547B IE SRV03

Note on Microsoft SQL Server software

The "SQL Server" software from Microsoft delivered with SIMATIC PCS 7 may not be used outside the SIMATIC PCS 7 environment without the written approval of Siemens.

SIMATIC NET S7-REDCONNECT Upgrade

1

 

2

OS standard software

 

 

 

 

 

 

SIMATIC PCS 7 OS Software Server V7.0

1

 

--

PCS 7 Server Redundancy V7.0, including RS 232

--

 

1

connecting cable, 10 m

 

 

 

Supplementary OS software (optional)

 

 

 

 

 

 

SIMATIC PCS 7 Archive V7.0/ SIMATIC PCS 7

1

 

2

Archive PowerPack for expansion of short-term

 

 

 

cyclic buffer archive

 

 

 

OS client

 

 

 

with Windows XP Professional operating system

 

 

 

SIMATIC PCS 7 Industrial Workstation including

 

 

 

operating system, alternatives

 

 

 

 

 

 

Connection for OS-LAN (terminal bus) onboard:

 

1

SIMATIC PCS 7 OS Client 547B WXP, alternatively

 

 

 

with:

 

 

 

• onboard standard graphics,

 

 

 

multi-VGA graphics card "2 Screens", or

 

 

 

multi-VGA graphics card "4 Screens"

 

 

 

OS standard software

 

 

 

SIMATIC PCS 7 OS Software Client V7.0

 

 

 

1

Supplementary OS software (optional)

 

 

 

 

 

 

SIMATIC PCS 7 SFC Visualization V7.0

 

1

SIMATIC Safety Matrix Viewer for PCS 7

 

1

 

 

 

 

Siemens ST PCS 7 · November 2007

5/9

Page 81
Image 81
Siemens ST PCS 7 manual OS software, Simatic PCS 7 ES/OS 547B IE WXP, With Windows 2003 Server operating system