Chapter 3 | Menus |
The material to be deposited is the most significant film parameter. However, a film definition also includes the setup parameters shown below:
Exit to
Main
Prev
Menu
Edit
Film
Conds.
Deposit
Controls
THICKNESS(kA) |
| RATE(A/s) | POWER( %) | ||
0.000 | 0.0 | 0.0 |
| ||
My Process 1 Editing: Aluminum |
|
| |||
|
|
|
|
|
|
Parameter |
| Value |
| Units |
|
|
|
|
|
|
|
|
|
|
|
|
|
P Term | 50 |
| None |
| |
|
|
|
|
|
|
I Term | 0.7 |
| Sec. |
| |
D Term | 0.0 |
| Sec. |
| |
Sensor 1 |
| On | On/Off |
| |
Sensor 2 |
| On | On/Off |
| |
Film Tooling | 100 |
| % |
| |
Output |
| Out1 | Out1/Out2 |
| |
1 |
|
|
| ||
Max Power | 76.0 |
| % |
| |
Slew Rate | 10.0 |
| % |
| |
Crystal Quality |
| Disabled |
|
| |
|
|
| |||
|
|
|
|
|
|
Film Edit Menu
Exit to Main
Prev
Menu
Edit
Returns to the Main Menu.
Returns to the Film Select Menu.
Selects the highlighted parameter for edit. SoftKey functions change to:
Next: Store parameter and move to next for editing.
Cancel: Stop editing and undo changes to selected parameter.
Enter: Stop editing and save values for selected parameter.
Control Knob: Turn to adjust value. Push to store value and move to next parameter.
Film Conds. Displays pre/post conditioning settings (See 2.6).
Deposit Controls Displays deposition control settings (See 2.2).
Control Knob Scrolls through the list of film parameters.