Panel Calibration

Panel Calibration

This section outlines the steps for calibrating the touch panel. It is recommended that you calibrate the panel before its initial use and after completing a firmware download.

Modero panels are factory setup with specific demo touch panel pages. The first splash screen that appears indicates the panel is receiving power, beginning to load firmware, and preparing to display the default touch panel pages. When the panel is ready, the AMX Splash Screen is replaced by the Initial Panel Page (FIG. 45).

AMX Splash Screen

Initial Panel Page

(appears during power-up)

(AMX Logo Page)

FIG. 45 AMX splash screen and initial Panel Page

 

Calibrating the Modero Panel

1.Press and hold the grey Front Setup Access button (FIG. 46) for 6 seconds to pass-over the Setup page and access the Calibration setup page (FIG. 47).

Front Setup

Access button (grey)

3 second press/hold:

Opens the Setup page

6 second press/hold:

Opens the Calibration page

Single press puts the panel to sleep

FIG. 46 Location of Front Setup Access button

2.Press the crosshairs (on the Calibration page) to set the calibration points on the LCD (FIG. 47).

3.After the "Calibration Successful.." message appears, press anywhere on the screen to continue and return to the Setup page.