Installing the Device
3.4INSTALLING THE DEVICE
The
To prevent possible personal injury and/or damage to the unit, do NOT connect power to the device until instructed to do so.
3.4.1Tabletop or Shelf Installation
The following two subsections provide guidelines for installation on a tabletop or shelf.
Guidelines for Tabletop and Shelf Installations
Tabletop and shelf installations must be within reach of the network cabling and meet the requirements listed below:
•Locate the
•In a shelf installation, ensure that the shelf can support 13.6 kg (30 lb) of static weight for each device.
•Maintain a temperature between 5°C (41°F) and 40°C (104°F) at the installation site with fluctuations of less than 10°C (18°F) per hour.
•Maintain a
Installation
For a tabletop or shelf installation, locate the device within seven feet of its power source and with an unrestricted free surface area as shown in Figure
To ensure proper ventilation and prevent overheating, leave a
!minimum clearance space of 5.1 cm (2.0 in) at the left, right,
CAUTION | and rear of the device. |
|
|