Chapter 11 Specifications

This section provides the following specifications for the Eaton 9170+ models:

SElectrical input and output

SModel specifications

SEnvironmental and safety

SBattery

SWeights and dimensions

Table 14. Electrical Input and Output

Nominal Input Voltage

200–240 Vac or 100/200, 110/220, 120/208, 120/240, 127/220 Vac

 

 

Input Voltage Range

176–276 Vac*

 

 

Nominal Output Voltage

200–240 Vac or 100/200, 110/220, 120/208, 120/240, 127/220 Vac

 

 

Nominal Frequency

Online: 50/60 Hz auto-sensing; output frequency tracks input frequency

 

to selectable limit (±0.1 to ±5.0 Hz; ±3.0 Hz default); switches to battery

 

operation outside this tolerance

 

On battery: 50 Hz or 60 Hz ±0.1 Hz

 

 

Regulation

±3% load regulation (under any line, load, or battery condition)

 

 

Voltage Waveform

Sine wave; <3% THD at rated linear loads, computer-grade power

 

 

Overload Capability

150% for 10 seconds; 300% for 12 cycles

 

 

DC Input Protection

DC fuse and battery charger overvoltage limit network

 

 

Output Protection

Microprocessor-sensed overvoltage and overcurrent, with fuse backup

 

 

Efficiency in Double-Conversion mode

>88%

 

 

Efficiency in Bypass mode

>96%

 

 

*176–250 Vac for universal power modules producing 200 and 208 Vac nominal output voltage. 152–239 Vac for 120/208 and 127/220.

Table 15. Application of Neutral to Ground Bonding

Models 0650C and 0660C Output ±3% load regulation (under any line, load, or battery condition)

Neutral-to-Ground Bonding Neutral is carried through from input to output; a separate neutral-to-ground bond is not required.

Eaton 9170+ UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality

97

Page 103
Image 103
Eaton Electrical ASY0674, ASY0673, ASY0529, ASY0567 Electrical Input and Output, Application of Neutral to Ground Bonding