UPS STARTUP

Startup for Plug-Receptacle Units

To start a plug-receptacle unit:

1.Plug the power cable of the unit into an approved, functional power outlet.

2.If external battery cabinets are installed, check the cable connections between the UPS and external battery cabinets.

Close the DC disconnect switch button on the back of each external battery cabinet. Insert the switch key supplied with the cabinet into the button and turn clockwise 1/2-turn. Pull the button out to close the switch. Turn the key back counter-clockwise, and remove the key.

3.Ensure that all power modules are properly installed and latched into the UPS cabinet.

4.If you are installing power management software, connect your computer to the UPS communication port (shown in Figure 49) using the supplied communication cable.

DB-9 Communication Port for Computer Cable

Figure 49. Communication Port

5.The UPS front panel display automatically turns on whenever input power is present and at least one power module is installed. Set up the initial operating parameters through the front panel display (see Initial Startup Parameters” on page 74).

NOTE The unit has no physical On/Off switch. Access the UPS On/Off function through the front panel display.

NOTE If the UPS has been manually set to operate in Bypass or Battery mode, change the System Control Mode Preference (menu 4 1) selection to Auto to return to normal Auto mode operation.

Eaton 9170+ UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality