Eaton Electrical ASY0673, ASY0529 Critical Alarm Messages, Alarm Message What It Means What to Do

Models: ASY0673 ASY0529 ASY0674 ASY0567

1 124
Download 124 pages 26.4 Kb
Page 116
Image 116

TROUBLESHOOTING

When an alarm occurs, follow these steps:

1.Observe the display to see which alarm is active.

NOTE To find out if more than one alarm is active, press . This switches the display between alarm messages. To silence the audible alarm, press button (A) below the display.

2.Find the alarm message in Table 22 or Table 23 and follow the instructions to resolve the problem. To clear an alarm after resolving the problem, press button (B) below the display. If the problem is still present, the alarm will sound again after a short delay.

Table 22 contains descriptions of critical alarm messages. Critical alarms require immediate operator attention and corrective action.

Table 22. Critical Alarm Messages

Alarm Message

What It Means

What to Do

 

 

 

A Low Battery

The UPS has shut down after running

 

on battery and discharging the

 

batteries.

Wait for AC input power to be restored. When AC input power returns, the UPS begins recharging batteries and applies power to the load.

C High Battery

The battery voltage is too high

Contact your service representative.

 

because of a charger problem,

 

 

battery problem, or incorrect

 

 

parameter setting.

 

 

 

 

E Low AC Output

The UPS has shut down because the

Contact your service representative.

 

AC output voltage is too low to

 

 

provide power to the load.

 

 

 

 

F High AC Output

The UPS has shut down because the

Contact your service representative.

 

AC output voltage is too high.

 

 

 

 

S High AC Input

The AC input voltage is too high; any

This alarm automatically clears when input voltage

 

further increase to the voltage may

returns to normal limits. The UPS will continue to

 

damage the UPS.

support the load until the batteries are depleted.

 

 

 

G Output Overload

The load is requiring more power

Switch off your equipment one piece at a time until

 

than the UPS power modules are

the alarm stops.

 

capable of supplying, and the UPS

 

 

has switched to Bypass mode.

 

 

 

 

I Overload Shutdown

The UPS has shut down due to

Remove excess load(s) from the UPS output and

 

excessive load.

restart the UPS by pressing the ON button through

 

 

the front panel display.

 

 

 

H High Heatsink

The inverter temperature is too high.

If the UPS has not shut down, bypass the UPS or shut

Temperature

If the temperature reaches a preset

down your equipment, and turn the UPS off. Contact

 

limit, the unit will shut down.

your service representative.

 

 

 

110

Eaton 9170+ UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality

Page 116
Image 116
Eaton Electrical ASY0673, ASY0529, ASY0567, ASY0674 manual Critical Alarm Messages, Alarm Message What It Means What to Do