OPERATION

Reading the Eaton 9170+ System Logs

The Eaton 9170+ system makes an entry in its logs each time it sounds an alarm or runs on battery power. This information can help in diagnosing power problems. You can display the UPS Inverter and Alarm logs on the front panel display in menu 2.

Inverter Log

The inverter (Battery mode) log is in menu 2 1. Move through the menu structure by pressing the Menu button and pressing the B button to move down to menu 2. Press to move to submenu 1 and press again to view the most recent entry in the inverter log.

The log stores up to 10 entries, in chronological order. Use the B and Y buttons to scroll up and down through the log entries. Each entry shows the date and time the unit switched to battery operation (in 24-hour format) and the duration of battery operation (in hours and minutes).

A typical Inverter Log entry is shown in Figure 57:

2

1

1

#0

I

 

09/29 13:56 01:04

Line Fault

Slot Top ESC

Figure 57. Inverter Log Entry

Figure 57 displays the most recent inverter log (2 1 1). If the unit is still running on inverter (battery power), an asterisk (*) appears beside the date. The Battery mode operation occurred on “09/29” (September 29) at “13:56” (1:56 p.m.), and the batteries supplied power for “01:04” (1 hour and 4 minutes).

Table 11 lists the inverter messages.

Table 11. Inverter Log Messages

Message

Explanation

 

 

Line Fault

UPS switched to battery because the input voltage was too high or low.

 

 

Battery Test

Battery test initiated inverter operation.

 

 

Manual

Operator initiated inverter operation.

 

 

84

Eaton 9170+ UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality