OPERATION
Off mode turns off the output and most internal circuitry. Within this mode, Sleep mode turns off all internal circuitry when AC line is not present and battery voltage drops to a low threshold. If AC input voltage is not present in Off mode, the user can direct the UPS to enter Sleep mode by selecting the Battery Protect (BP) feature (see “Removing Input Power” on page 79). When AC input voltage returns in the Off mode (caused by a low battery alarm condition), the UPS automatically recovers and, if the Auto Restart parameter is enabled, switches to Double Conversion mode. Auto Restart is enabled as a
After a discharge and subsequent
Figure 53 shows the basic functional elements of the UPS.
Input
(utility) Power
EMI/RFI
Filter
Battery
Modules (parallel)
Line/Battery
Relay
|
| Isolation |
Bypass Relay |
| Transformer |
| (an option only | |
|
| provided |
Input Power (boost) |
| on units |
DC/AC Power Inverter | manufactured | |
Converter | before 2009) | |
| Internal DC |
|
| Power Bus |
|
|
| Output Relay |
Battery Charger
Capacitor Bank
Figure 53. Eaton 9170+ UPS Functional Block Diagram
78 | Eaton 9170+ UPS |