Eaton Electrical ASY0529, ASY0673, ASY0567, ASY0674 manual Power Module Replacement

Models: ASY0673 ASY0529 ASY0674 ASY0567

1 124
Download 124 pages 26.4 Kb
Page 101
Image 101

MAINTENANCE

3.Pull the module out approximately 17 cm (7”) to the secondary stop on top of the module.

4.Press down on the secondary stop release, pull the module out farther, and support the module weight with your second hand as you remove the module from the cabinet.

5.Remove the battery module beside the first in a similar manner. Label the original modules with masking tape or some other identifier.

6.After removing a pair (one string) of battery modules, install a replacement pair. Replacements may be installed in empty cabinet slots before removing the original battery modules.

7.When all desired battery modules have been replaced, replace the front cover(s).

8.If the batteries are not properly installed, the Open Cell alarm activates. Check the batteries in the slot indicated on the alarm screen.

Power Module Replacement

The Eaton 9170+ hot‐swap feature lets you replace a power module without disconnecting the load or damaging the UPS.

NOTE The UPS may switch to internal Bypass mode if the remaining power modules are insufficient to supply the required power. If empty slots exist, install replacement modules before removing original ones.

Use care in removing and installing power modules. To remove a power module:

1.Remove the front cover.

The cover has spring latches on the left and right sides that hold it in place.

2.Loosen the thumbscrew on the module handle. Press down on the latch release at the center of the module handle and pull the handle down.

As the module handle fully extends, the module disconnects. Slide the module slowly out of the cabinet.

Eaton 9170+ UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality

95

Page 101
Image 101
Eaton Electrical ASY0529, ASY0673, ASY0567, ASY0674 manual Power Module Replacement