SPECIFICATIONS

Table 17. Model Specifications for Universal Power Modules (XXXXX-Model/03 and ASY-0674) (continued)

Nine- and Twelve-Slot Cabinet

CAUTION Do NOT install more than seven power and/or battery charger modules in a 9- or 12-slot cabinet.

Optional

UPS

Input Current for

Output Current for

Recommended

Heat

Chargers

kVA/Watts

200/208/220/230/240V

200/208/220/230/240V

Input Service

Dissipation

 

 

 

 

 

 

2

3/2100

46/45.5/45/44.5/44A

15/14.5/14/13/12.5A

60A

860W

 

 

 

 

 

(2.93 kBTU/hr)

 

 

 

 

 

 

3

3/2100

62/61.5/61/60.5/60A

15/14.5/14/13/12.5A

80A

1145W

 

 

 

 

 

(3.90 kBTU/hr)

 

 

 

 

 

 

4

3/2100

78/77.5/77/76.5/76A

15/14.5/14/13/12.5A

100A

1430W

 

 

 

 

 

(4.88 kBTU/hr)

 

 

 

 

 

 

5

3/2100

94/93.5/93/92.5/92A

15/14.5/14/13/12.5A

125A

1720W

 

 

 

 

 

(5.85 kBTU/hr)

 

 

 

 

 

 

0

6/4200

28/27/26/25/24A

30/29/28/26/25A

40A

570W

 

 

 

 

 

(1.95 kBTU/hr)

 

 

 

 

 

 

1

6/4200

44/43/42/41/40A

30/29/28/26/25A

60A

860W

 

 

 

 

 

(2.93 kBTU/hr)

 

 

 

 

 

 

2

6/4200

60/59/58/57/56A

30/29/28/26/25A

80A

1145W

 

 

 

 

 

(3.90 kBTU/hr)

 

 

 

 

 

 

3

6/4200

76/75/74/73/72A

30/29/28/26/25A

100A

1430W

 

 

 

 

 

(4.88 kBTU/hr)

 

 

 

 

 

 

4

6/4200

92/91/90/89/88A

30/29/28/26/25A

125A

1720W

 

 

 

 

 

(5.85 kBTU/hr)

 

 

 

 

 

 

5

6/4200

102A**

30/29/28/26/25A

125A

1995W

 

 

 

 

 

(6.75 kBTU/hr)

 

 

 

 

 

 

0

9/6300

42/40.5/39/37.5/36A

45/43.5/42/39/37.5A

60A

860W

 

 

 

 

 

(2.93 kBTU/hr)

 

 

 

 

 

 

1

9/6300

58/56.5/55/53.5/52A

45/43.5/42/39/37.5A

80A

1145W

 

 

 

 

 

(3.90 kBTU/hr)

 

 

 

 

 

 

2

9/6300

74/72.5/71/69.5/68A

45/43.5/42/39/37.5A

100A

1430W

 

 

 

 

 

(4.88 kBTU/hr)

 

 

 

 

 

 

3

9/6300

90/88.5/87/85.5/84A

45/43.5/42/39/37.5A

125A

1720W

 

 

 

 

 

(5.85 kBTU/hr)

 

 

 

 

 

 

*In High-Efficiency and Bypass modes the input current equals the output current plus 2A for each power module in the system. For redundant power module operation (N+X), increase the input current rating by 2A for each additional redundant power module.

** Maximum current rating for the cabinet size. If an additional charger is desired, it must be installed in external battery cabinet XXXXX-Model/Batt4.

102

Eaton 9170+ UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality