SPECIFICATIONS
Table 17. Model Specifications for Universal Power Modules
Nine- and Twelve-Slot Cabinet
CAUTION Do NOT install more than seven power and/or battery charger modules in a 9- or
Optional | UPS | Input Current for | Output Current for | Recommended | Heat |
Chargers | kVA/Watts | 200/208/220/230/240V | 200/208/220/230/240V | Input Service | Dissipation |
|
|
|
|
|
|
2 | 3/2100 | 46/45.5/45/44.5/44A | 15/14.5/14/13/12.5A | 60A | 860W |
|
|
|
|
| (2.93 kBTU/hr) |
|
|
|
|
|
|
3 | 3/2100 | 62/61.5/61/60.5/60A | 15/14.5/14/13/12.5A | 80A | 1145W |
|
|
|
|
| (3.90 kBTU/hr) |
|
|
|
|
|
|
4 | 3/2100 | 78/77.5/77/76.5/76A | 15/14.5/14/13/12.5A | 100A | 1430W |
|
|
|
|
| (4.88 kBTU/hr) |
|
|
|
|
|
|
5 | 3/2100 | 94/93.5/93/92.5/92A | 15/14.5/14/13/12.5A | 125A | 1720W |
|
|
|
|
| (5.85 kBTU/hr) |
|
|
|
|
|
|
0 | 6/4200 | 28/27/26/25/24A | 30/29/28/26/25A | 40A | 570W |
|
|
|
|
| (1.95 kBTU/hr) |
|
|
|
|
|
|
1 | 6/4200 | 44/43/42/41/40A | 30/29/28/26/25A | 60A | 860W |
|
|
|
|
| (2.93 kBTU/hr) |
|
|
|
|
|
|
2 | 6/4200 | 60/59/58/57/56A | 30/29/28/26/25A | 80A | 1145W |
|
|
|
|
| (3.90 kBTU/hr) |
|
|
|
|
|
|
3 | 6/4200 | 76/75/74/73/72A | 30/29/28/26/25A | 100A | 1430W |
|
|
|
|
| (4.88 kBTU/hr) |
|
|
|
|
|
|
4 | 6/4200 | 92/91/90/89/88A | 30/29/28/26/25A | 125A | 1720W |
|
|
|
|
| (5.85 kBTU/hr) |
|
|
|
|
|
|
5 | 6/4200 | 102A** | 30/29/28/26/25A | 125A | 1995W |
|
|
|
|
| (6.75 kBTU/hr) |
|
|
|
|
|
|
0 | 9/6300 | 42/40.5/39/37.5/36A | 45/43.5/42/39/37.5A | 60A | 860W |
|
|
|
|
| (2.93 kBTU/hr) |
|
|
|
|
|
|
1 | 9/6300 | 58/56.5/55/53.5/52A | 45/43.5/42/39/37.5A | 80A | 1145W |
|
|
|
|
| (3.90 kBTU/hr) |
|
|
|
|
|
|
2 | 9/6300 | 74/72.5/71/69.5/68A | 45/43.5/42/39/37.5A | 100A | 1430W |
|
|
|
|
| (4.88 kBTU/hr) |
|
|
|
|
|
|
3 | 9/6300 | 90/88.5/87/85.5/84A | 45/43.5/42/39/37.5A | 125A | 1720W |
|
|
|
|
| (5.85 kBTU/hr) |
|
|
|
|
|
|
*In
** Maximum current rating for the cabinet size. If an additional charger is desired, it must be installed in external battery cabinet
102 | Eaton 9170+ UPS |