UPS WITH BYPASS ELECTRICAL INSTALLATION
Input Current Ratings
Table 1 contains the required circuit breaker ratings for hardwired installations. Circuit breaker ratings for units having an input line cord are determined by the current capacity of the line cord.
Table 1. Required Input Circuit Breaker Sizes (200–240 Vac, 50/60 Hz)
UPS Capacity | Input Circuit Breaker Rating |
|
|
3 kVA | 25A |
|
|
6 kVA | 40A |
|
|
9 kVA | 60A |
|
|
12 kVA | 80A |
|
|
15 kVA | 100A |
|
|
18 kVA | 125A |
|
|
NOTE If you are installing an optional battery charger module, refer to that user's guide for the proper input circuit breaker sizes and ratings.
C A U T I O N
To accommodate the feature of easy system expandability, it is recommended that initial installation of the Eaton 9170+ UPS contains wiring to support the maximum capacity of the UPS cabinet: 3 kVA for